Free air intake only with a straight duct section of
1B upstream.

Installing the CAV controller

Personnel:

HVAC technician for Ex areas

Protective equipment:

Industrial safety helmet

Protective gloves

Safety shoes

 WARNING!

Risk of explosion from the commissioning of
damaged products

Commissioning damaged products in areas with
potentially explosive atmospheres may lead to an
explosion. This can cause serious or even fatal
injuries as well as considerable damage to prop-
erty.

Before you install the controller, check it for
damage that could impair the movement of the
damper blade; if the controller has been dam-
aged, replace it.

Before you install the product, take suitable precau-
tions to protect air distribution components from
contamination during installation (VDI 6022). If this
is not possible, at least cover the product or take
other precautions to protect it from contamination.
In this case you have to ensure that the product
cannot be started. Ensure that all components are
clean before you install them. If necessary, clean
them thoroughly. If you have to interrupt the installa-
tion procedure, protect all openings from the
ingress of dust or moisture.

Installation

 

CAV controllers EN-Ex

6

Summary of Contents for EN-Ex

Page 1: ...Ex are used for con stant volume flow control in ventilation and air con ditioning systems They can be used for supply air and extract air systems in the following areas with potentially explosive atm...

Page 2: ...pecially trained for work in areas with potentially explosive atmospheres They know the rules and regulations relevant to their work and to explosion protection Evidence of the relevant experience and...

Page 3: ...carrying out any work Wear protective gloves safety shoes and a hard hat Please note Be careful when unloading or moving the product and pay attention to the symbols and information on the packaging...

Page 4: ...0 EN EX 400 x 200 B H 400 M8 B H H B Fig 3 EN Ex D with acoustic cladding Nominal size Nom inal width B mm Nom inal height H mm B1 mm H1 mm EN Ex EN Ex D B2 mm H2 mm m kg B2 mm H2 mm m kg 200 100 200...

Page 5: ...284 676 326 14 680 330 22 600 300 600 300 634 334 676 376 15 680 380 22 600 400 600 400 634 434 676 476 18 680 480 26 600 500 600 500 634 534 676 576 19 680 580 29 600 600 600 600 634 634 676 676 20 6...

Page 6: ...controller check it for damage that could impair the movement of the damper blade if the controller has been dam aged replace it Before you install the product take suitable precau tions to protect a...

Page 7: ...sized fixing material fixing material is not included in the supply package The product must remain accessible for main tenance even after installation Important If there is a risk that the controller...

Page 8: ...nectors part of the supply package on both sides to the ducting It is also possible to connect the controller directly to the terminal point for equipoten tial bonding of the building This requires a...

Page 9: ...G Risk of explosion Ignition sources such as sparks open flames or hot surfaces can lead to explosions in an area with potentially explosive atmospheres Get written permission before you start working...

Page 10: ...explosive atmosphere To remove any potentially explosive atmos phere purge the system with fresh air before you work on it Use only tools that have been approved for use in areas with potentially exp...

Page 11: ...ause malfunction damage to property and total failure of equipment Use only original replacement parts from TROX Cleaning Please note The cleaning intervals given in the VDI 6022 standard apply Clean...

Page 12: ...Declaration of conformity Declaration of conformity CAV controllers EN Ex 12...

Reviews: