The actual scope of delivery may differ from the
information in this manual for special constructions,
additional order options or as a result of recent
technical changes.

Transport and storage

Delivery check

Upon delivery, carefully remove the packaging and
check the unit for transport damage and complete-
ness. In case of any damage or an incomplete ship-
ment, contact the shipping company and your sup-
plier immediately. Put the product back into its
packaging after the delivery check to protect it from
dust and contamination.

 Fixing and installation material

Fixing and installation material is not part of the
supply package (unless stated otherwise), but
has to be provided by others; it has to be suitable
for the installation situation.

Transport on site

 CAUTION!

Danger of injury from sharp edges, sharp cor-
ners and thin sheet metal parts!

Sharp edges, sharp corners and thin sheet metal
parts may cause cuts or grazes.

Be careful when carrying out any work.

Wear protective gloves, safety shoes and a
hard hat.

Please note:

Be careful when unloading or moving the
product, and pay attention to the symbols and
information on the packaging.

If possible, take the product in its transport
packaging up to the installation location.

Use only lifting and transport gear designed for
the required load.

Always secure the load against tipping and
falling.

Do not move bulky items just by yourself. Get
help to prevent injuries and damage.

Storage

Please note:

Store the product only in its original packaging

Protect the product the effects of weather

Protect the product from humidity, dust and
contamination

Storage temperature: -10 °C to 50 °C.

Relative humidity: 95% max., no condensation

Packaging

Properly dispose of packaging material.

Technical data

Nominal sizes

200 × 100 to 600 × 600 m
m

Volume flow rate range

40 – 3360 l/s or 144 –
 12096 m³/h

Volume flow rate control
range

Approx. 25 to 100% of the
nominal volume flow rate

Scale accuracy

± 4%

Minimum differential pres-
sure

50 Pa

Maximum differential pres-
sure

1000 Pa

Operating temperature

10 – 50 °C

Transport and storage

 

CAV controllers EN-Ex

3

Summary of Contents for EN-Ex

Page 1: ...Ex are used for con stant volume flow control in ventilation and air con ditioning systems They can be used for supply air and extract air systems in the following areas with potentially explosive atm...

Page 2: ...pecially trained for work in areas with potentially explosive atmospheres They know the rules and regulations relevant to their work and to explosion protection Evidence of the relevant experience and...

Page 3: ...carrying out any work Wear protective gloves safety shoes and a hard hat Please note Be careful when unloading or moving the product and pay attention to the symbols and information on the packaging...

Page 4: ...0 EN EX 400 x 200 B H 400 M8 B H H B Fig 3 EN Ex D with acoustic cladding Nominal size Nom inal width B mm Nom inal height H mm B1 mm H1 mm EN Ex EN Ex D B2 mm H2 mm m kg B2 mm H2 mm m kg 200 100 200...

Page 5: ...284 676 326 14 680 330 22 600 300 600 300 634 334 676 376 15 680 380 22 600 400 600 400 634 434 676 476 18 680 480 26 600 500 600 500 634 534 676 576 19 680 580 29 600 600 600 600 634 634 676 676 20 6...

Page 6: ...controller check it for damage that could impair the movement of the damper blade if the controller has been dam aged replace it Before you install the product take suitable precau tions to protect a...

Page 7: ...sized fixing material fixing material is not included in the supply package The product must remain accessible for main tenance even after installation Important If there is a risk that the controller...

Page 8: ...nectors part of the supply package on both sides to the ducting It is also possible to connect the controller directly to the terminal point for equipoten tial bonding of the building This requires a...

Page 9: ...G Risk of explosion Ignition sources such as sparks open flames or hot surfaces can lead to explosions in an area with potentially explosive atmospheres Get written permission before you start working...

Page 10: ...explosive atmosphere To remove any potentially explosive atmos phere purge the system with fresh air before you work on it Use only tools that have been approved for use in areas with potentially exp...

Page 11: ...ause malfunction damage to property and total failure of equipment Use only original replacement parts from TROX Cleaning Please note The cleaning intervals given in the VDI 6022 standard apply Clean...

Page 12: ...Declaration of conformity Declaration of conformity CAV controllers EN Ex 12...

Reviews: