EM-LON Operating Manual / Leaflet no. M375EV4 (3/2013)
8
5
LonWorks network variables
Name of variable
Data type
FH
RR
TA
M
RR RMF
T
AM RMF
Meaning
nviSunblinder
SNVT_switch
x
x
Control input signal for sun protection/blinds
nviVolflowExh
SNVT_flow
x
x
x
x
x
Connection of an extract air flow
nviVolflowSuph
SNVT_flow
x
x
x
x
x
Connection of a supply air flow
nvoSystemDevices
SNVT_count
x
x
x
x
x
Number of EASYLAB controllers
nvoStateDIO
SNVT_state
x
x
x
x
x
State of the digital inputs and outputs (TCU3)
Overview of additional data points for EM-LON LonWorks interface firmware version 2.0,
and TCU firmware version 3.0
Name of variable
Data type
FH
RR
TA
M
RR RMF
T
AM RMF
Meaning
nviSC_LockHP
SNVT_switch
x
Automatic sash device
Close and lock sash - HighPrio
nvoSC_LockHP
SNVT_switch
x
Automatic sash device
Feedback, sash has been locked - HighPrio
nviSC_SetPos
SNVT_switch
x
Automatic sash device
Default setting from central BMS: Close sash
nvoSC_GetPos
SNVT_switch
x
Automatic sash device
Position status
nvoSC_Alarm
SNVT_switch
x
Automatic sash device
Alarm
Overview of additional data points for EM-LON LonWorks interface firmware version 2.0,
and TCU firmware version 4.0