Technical data
Designation
Value
Primary air volume flow rate
9 – 97 l/s, 32 – 350 m³/h
Cooling capacity
Up to approx. 2150 W
Heating capacity
Up to approx. 2000 W
Max. operating pressure, water side
6 bar
Max. operating temperature
75 °C
(55 °C when using flexible connecting hoses)
Minimum operating temperature
6 °C
Dimensions
L1
L2
634
595
H
L
Z
82
8
Z
175
X
105
105
A
∅D
385
B
X
࿆
࿇
Fig. 2: Dimensional drawing of DID614
Ⓐ
4-pipe
Ⓑ
2-pipe
Technical data
Active chilled beams Type DID614
4