Cleaning
Cleaning the casing
The casing may be cleaned with a damp cloth.
Sticky dirt or contamination may be removed with a
commercial, non-aggressive cleaning agent.
Cleaning agents that contain chlorine must not be
used.
Cleaning the heat exchanger
Personnel:
Specialist personnel
Protective equipment:
Industrial safety helmet
Safety shoes
Protective gloves
1.
Remove the induced air grille,
Ä
on page 11
Fig. 13: Cleaning the heat exchanger
2.
Carefully clean the heat exchanger with an
industrial vacuum cleaner. Be careful to not
damage the fins. We recommend using a
soft brush on the suction inlet.
3.
After cleaning, re-attach the safety cables,
and screw-fix and close the grille.
CAUTION!
Danger of head injuries from the fall of
the induced air grille!
Check that the induced air grille and
safety cables are securely fixed!
Cleaning
Active chilled beams Type DID614
12