background image

Important notes

Information on the installation manual

This manual enables operating or service personnel
to correctly install the product described below and
to use it safely and efficiently.

It is essential that these individuals read and fully
understand this manual before starting any work.
The basic prerequisite for safe working is to comply
with the safety notes and all instructions in this
manual.

The local regulations for health and safety at work
and general safety regulations also apply.

Qualified staff

Specialist personnel

Specialist personnel are individuals who have suffi-
cient professional or technical training, knowledge
and actual experience to enable them to carry out
their assigned duties, understand any potential haz-
ards related to the work under consideration, and
recognise and avoid any risks involved.

Specialized personnel

Specialised personnel are personnel, who due to
their specialized training, skills, and experience, as
well as knowledge of the applicable standards and
regulations, are capable of executing the tasks
assigned to them, and of recognizing possible haz-
ards and avoiding them on their own.

Limitation of liability

The information in this manual has been compiled
with reference to the applicable standards and
guidelines, the state of the art, and our expertise
and experience of many years.

The manufacturer does not accept any liability for
damages resulting from:

Non-compliance with this manual

Incorrect use

Operation or handling by untrained individuals

Unauthorised modifications

The actual scope of delivery may differ from the
information in this manual for special constructions,
additional order options or as a result of recent
technical changes.

Personal protective equipment

Personal protective equipment must be worn for all
work in order to reduce health or safety hazards to
the minimum.

The appropriate protective equipment for a job must
be worn for as long as the job takes.

Industrial safety helmet

Industrial safety helmets protect the head from
falling objects, suspended loads, and the effects of
striking the head against stationary objects.

Protective gloves

Protective gloves protect hands from friction, abra-
sions, punctures, deep cuts, and direct contact with
hot surfaces.

Safety shoes

Safety shoes protect the feet against crushing,
falling parts, and slipping on slippery ground.

Correct use

Active chilled beams provide centrally conditioned
primary air (fresh air) to the room. Heat exchangers
are used for additional cooling and/or heating.

Important notes

 

Active chilled beams Type DID614

2

Summary of Contents for DID614

Page 1: ...ater connections Encasement optional Heat exchanger Front frame Induced air grille Installation manual en GB Active chilled beams Type DID614 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germa...

Page 2: ...this manual has been compiled with reference to the applicable standards and guidelines the state of the art and our expertise and experience of many years The manufacturer does not accept any liabil...

Page 3: ...ct use Incorrect use of the unit can lead to dangerous situations Never use the unit in areas with potentially explosive atmos pheres in humid rooms in rooms with aggressive or dust laden air Importan...

Page 4: ...ty Up to approx 2000 W Max operating pressure water side 6 bar Max operating temperature 75 C 55 C when using flexible connecting hoses Minimum operating temperature 6 C Dimensions L1 L2 634 595 H L Z...

Page 5: ...1147 1069 119 L total length grille B total width grille Variants for freely suspended installation Dimensions mm L B L1 L2 X 900 900 522 444 257 5 1525 900 1147 1069 257 5 L total length grille B tot...

Page 6: ...g 3 Carrying the unit in pairs Use only lifting and transport gear designed for the required load Always secure the load against tip ping and falling Upon delivery carefully remove the packaging and c...

Page 7: ...593 618 8 Fig 4 Ceiling installation visible T bars DID614 Ceiling tile 598 623 8 Fig 5 Ceiling installation with clamping profile DID614 Ceiling tile 8 598 623 Fig 6 Ceiling installation concealed T...

Page 8: ...ible remove the adjacent ceiling tiles Only work in pairs preferably use a lift DANGER Danger of death from the fall of suspended loads Only use fixing materials designed for the required load Use all...

Page 9: ...e hoses accessory G 1 2 union nut and flat seal SW24 Screw connection rigid Flexible hoses accessory Connecting the unit screw connection Personnel Specialist personnel Protective equipment Industrial...

Page 10: ...and free from residues and foreign matter Ensure that the water system including the heat exchanger has been filled and vented Setting the air control blades The air discharge pattern can be changed...

Page 11: ...ir grille Fig 11 1 pull it down To completely remove the grille unhook the safety cables Fig 11 2 by pulling them down together with the retaining plates Fig 11 3 Fig 12 Adjusting the nozzles on the D...

Page 12: ...y shoes Protective gloves 1 Remove the induced air grille on page 11 Fig 13 Cleaning the heat exchanger 2 Carefully clean the heat exchanger with an industrial vacuum cleaner Be careful to not damage...