adjust the actuator, press the green 'Adap-
tion' button. The status LED lights up
(orange) and the actuator is moved to its
end position. When adjustment is complete,
the status LED goes off.
Adaptation of the actuator (only for fast-running
actuator TROX TUSD)
5.
For air terminal units with TROX type HPD
actuator (A00000067751), adaptation must
be carried out during commissioning. This
ensures that any incorrect position, e.g. due
to shipping or installation, is corrected.
To do this, press the
‘diagnostics
è
push button Adaption’
in the EasyCon-
nect software.
For adaptation, the actuator moves to the
end positions and then automatically
switches to control mode.
Functional test
6.
To complete commissioning, perform a func-
tional test of the controller using the Easy-
Connect software, taking into account the
project specifications for the required oper-
ating modes.
Compare the volume flow rate setpoint value
for each operating mode with the actual
value and document the results. Check if
alarms are emitted and signaled with the
functional test.
Commissioning
Control components for VAV terminal units TROX UNIVERSAL
27