External interfaces
No.
Name
Connection
point for
Description
6
(X1)
Door contact
Connection for a volt-free door contact switch (only for room pressure con-
trol)
7
Terminal-1 (X2) Control panel 1
Connection point for:
EASYLAB control panel BE-LCD
PC with EasyConnect software
–
BlueCon adapter
–
Special configuration cable
Tablet or smartphone with Android app EasyCon
–
BlueCon adapter
Terminal-2 (X3) Control panel 2
8
Actuator (X4)
Actuator
The actuator of the damper blade is factory fitted.
9
Sensor (X5)
Analogue input
AI5
For room or duct pressure control for connection of the pressure sensor,
otherwise for connection of variable extract air/supply air volume flow rates
can be used by 0-10 V DC signals. (Characteristic can be configured)
10
Comm-1 (X6)
Communication 1 RJ45 socket for SF-UTP network patch cables
Comm-2 (X7)
Communication 2
For details on the electrical data for each connection see
‘List of terminal connections’ on page 36
Product description
Control components for VAV terminal units TROX UNIVERSAL
15