No.
Name
Description
LED off
24 V supply voltage failed / sagging
5
Connection of mains
supply
Connection for EM-TRF and EM-TRF-USV expansion modules
6
Status display for digital
inputs DI1…DI6
LED on
Digital input DI is active
LED off
Digital input DI is not active
7
Status display for digital
outputs DO1…DO6
LED on
Digital output DO is active
LED off
Digital output DO not active
8
Terminal block DO1…DO6 Digital outputs 1...6
Changeover relays
max. 250 V AC 8 A, switch-on current 12 A max.
9
Terminal block, 24 V
Supply voltage 24 V AC or 24 V DC
Do not use 24 V AC and 24 V DC power supplies at the same time!
10
Terminal block AO1... AO3 Analogue outputs 1...3
Can be configured for 0-10 V DC, 10 mA max.
11
Terminal block DI2…DI6
Digital inputs 2...6
For volt-free switch contacts 5 V DC xx mA
12
Terminal block TI1
Input for temperature sensor PT1000 (not supported)
13
Terminal block AI1…AI4
Analogue inputs 1...4
Can be configured for 0-10 V DC, 10 mA max.
14
Clip / connection
Strain relief / connection for communication cable shield
15
Functional earth
Connection point for the functional earth to improve electromagnetic compatibility
(EMV)
16
COMM-1 connection
COMM-2 connection
Alternative terminals for the communication cable; in general, however, connection
points Comm-1 (X6) and Comm-2 (X7) should be used (
SF-UTP network cable
17
COMM terminal resistor
Switch ON
Communication cable termination is active
Switch OFF
Communication cable termination is inactive
18
Terminal 3
Connection for TROX HPD actuator
Do not connect PD here
For details on the electrical data for each connection see
‘List of terminal connections’ on page 36
Product description
Control components for VAV terminal units TROX UNIVERSAL
17