VolflowAct
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Output of the volume flow rate actual value of the
volume flow controller
Data point
BACnet: Analog Value Object – Instance 2
Modbus: Register 3
VolTotalExh
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Output of the total extract air volume flow rate of an
room
This includes the extract air volume flow rates of all
fume cupboards and extract air contollers as well as
any additional extract air volume flow rates (constant
and variable) from other controllers.
Data point
BACnet: Analog Value Object – Instance 3
Modbus: Register 7
VolTotalSup
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Output of the total supply air flow rate of an room
This includes the supply air volume flow rates of all
supply air controllers as well as any additional supply
air volume flow rates (constant and variable).
Data point
BACnet: Analog Value Object – Instance 4
Modbus: Register 8
PressSet
BMS access: RD
Equipment function:
EASYLAB
–
RR with RMF, TAM with RMF
TROX UNIVERSAL
–
PR*/PD*, PR*/PD* with RMF
Unit: Pa
Function
Output of the differential pressure control setpoint
value within the system
Data point
BACnet: Analog Value Object – Instance 5
Modbus: Register 12
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
28