Analogue Value Objects
In-
stanc
e
Description
Unit
Unit
Acc-
ess
Sup-
port
COV
TCU3
TAM
TROX UNIVERSAL
Available with equipment function
FH
RR
RR
RMF
EC,
SC
TAM TAM
RMF
RS/
RE
RS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
1
VolflowSet
l/s
(87)
x
x
x
x
x
x
x
RD
N
2
VolflowAct
l/s
(87)
x
x
x
x
x
x
x
x
x
RD
N
3
VolTotalExh
l/s
(87)
x
x
x
x
x
x
x
x
x
x
RD
N
4
VolTotalSup
l/s
(87)
x
x
x
x
x
x
x
x
x
x
RD
N
5
PressSet
pa
(53)
x
x
x
x
RD
N
6
PressAct
pa
(53)
x
x
x
x
RD
N
7
VelocitySet
m/s
(74)
x
RD
N
8
VelocityAct
m/s
(74)
x
RD
N
9
WireSen-
sorPos
%
(98)
x
RD
N
10
DampPos
%
(98)
x
x
x
x
x
x
x
x
RD
N
11
Damp-
PosMax_FH
%
(98)
x
x
x
x
x
x
RD
N
12
Damp-
PosMin_FH
%
(98)
x
x
x
x
x
x
RD
N
13
Damp-
PosMax_RE
%
(98)
x
x
x
x
x
x
x
x
x
x
RD
N
14
Damp-
PosMin_RE
%
(98)
x
x
x
x
x
x
x
x
x
x
RD
N
15
Damp-
PosMax_TE
%
(98)
x
x
x
x
x
x
x
x
x
x
RD
N
16
Damp-
PosMin_TE
%
(98)
x
x
x
x
x
x
x
x
x
x
RD
N
17
Damp-
PosMax_RS
%
(98)
x
x
x
x
x
x
x
x
x
x
RD
N
18
Damp-
PosMin_RS
%
(98)
x
x
x
x
x
x
x
x
x
x
RD
N
19
VolOffset_T
%
(98)
x
x
WR,
RD
N
20
VolOffset_P
%
(98)
x
x
WR,
RD
N
Abbreviations
Interface information
BACnet interface
Expansion module EM-BAC-MOD-01
12