RoomModeAct
BMS access: RD
Equipment function:
EASYLAB
–
RR with RMF, TAM with RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Output of the room operating mode
For more information on each operating mode see
the description of the 'Mode' input variable
Functional values (BACnet / Modbus)
1/0 = No default
2/1 = Standard mode
3/2 = Reduced operation
4/3 = Increased operation
5/4 = Shut-off
6/5 = OPEN position
Data point
BACnet: Multistate Value Object – Instance 4
Modbus: Register 36
SwitchPos
BMS access: RD
Equipment function:
EASYLAB
–
FH
TROX UNIVERSAL
–
not used
Function
Output of the current switching step of the fume cup-
board as a numeric value if the fume cupboard con-
troller is equipped with switch contacts for 2-point or
3-point control (FH2P, FH-3P)
Data point
BACnet:
Multistate Value Object – Instance 5
–
1 = invalid state
–
2 = switching step 1
–
3 = switching step 2
–
4 = switching step 3
Modbus:
Register 35
–
0 = invalid state
–
1 = switching step 1
–
2 = switching step 2
–
3 = switching step 3
SC_GetLockHighPrio
Equipment function: not available
VolflowSet
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF
Unit: l/s
Function
Output of the volume flow rate setpoint value for the
volume flow controller
Data point
BACnet: Analog Value Object – Instance 1
Modbus: Register 4
Interface information
Data points – detailed description > Output variables