background image

TX-INP1

 

9

TX-INP1 SPECIFICATIONS

AURASAFE mini input-module for

smokedetector/fire thermostat

Technical data

Inputs

Monitored input for fire alarm system /
smoke detector. 2K2 end resistor must be
mounted.

Addressing

DIP-switch

Indicator

LED on the side

Terminals

Springclamps, max. 2,5 mm

2

Dimensions

85x85x40 mm

WIRING TERMINALS

A.  Fire alarm system / Smoke detector input

 

 

Up to two smoke detectors can be connected in a 

 

 

series. 2,2 kohm resistance must be mounted on 

 

 

the last smoke detector.

B.  Supply/Bus input

 

 

2-wire bus supply. Two extra terminal-pairs for 

 

 

forwarding.

C.  Addressing DIP-switch

 

 

See separate description for addressing.

D.  Reset-button

 

 

See separate description.

E.  Cable fixation

F.  LED indicator

 

 

See separate description for indicator.

LED indicators

Status

Green

OK

Green, blinking slowly

Reset smoke detector

Blue, blinking slowly

Service detector

Red, blinking slowly

Alarm

ADDRESSING

The module is assigned an address via the DIP switches. It is not

necessary for the modules to be placed in order during assembly.

If the module is connected to a fire alarm, choose an address

between 0 - 99. If it is connected to a smoke detector, choose an

adress between 100-119.

Each of the 7 switches represents a value, as indicated on the right.

The sum of the activated switches gives the module address. As

Example 1 shows, switches 1, 3 and 6 are activated. They each count

for 1 + 4 + 32, ie the module’s address becomes 37.

The same address must not be given to more than one damper.

MANUAL RESET OF SMOKE DETECTOR

By using the reset button it is possible to perform a manual reset of a

connected smoke detector. The button is held down until the LED

indicator starts blinking rapidly and the output is reset.

Value:

Example 2: 

 

Address:

2 + 8 + 16 + 64 = 90

Example 1: 

 

Address:

1 + 4 + 32 = 37

Summary of Contents for Auranor AURASAFE mini

Page 1: ...rs up to 100 fire dampers Digital error signal Connection to BMS by Modbus GB0351 02 22 AURASAFE mini Monitoring and control of fire dampers TROX Auranor Norge AS Auranorvegen 6 NO 2770 Jaren Phone 47...

Page 2: ...fe Mini 1 TX CTRL1 Controller std 12 Dampers 2 TX CTRL2 Controller lite 8 Dampers 3 TX BO1 Boostermodule 4 TX BRS3 Dampermodule for fire and smoke dampers 5 TX RKS1 Dampermodule for smoke control damp...

Page 3: ...and booster modules must have a 230V supply Figure 3 You can use the TX DREL1 Relay module to distribute the relay output of the AHU to 4 units TX INP1 Input module is used if smoke detector or fire...

Page 4: ...wire bus for supply and communication with bus modules E Alarm relay output F Smoke fan ventilated system relay output G Service relay output Indicates if service is required for smoke detectors H Ve...

Page 5: ...re bus for supply and communication with bus modules E Alarm relay output F Smoke fan ventilated system relay output G Service relay output Indicates if service is required for smoke detectors H Venti...

Page 6: ...Supply B Supply Bus output for damper modules Extended 2 wire bus for supply and communication with dampers C Bus input 2 wire bus input from existing network D LED indicators See separate description...

Page 7: ...1 Red blinking slowly ADDRESSING The damper module is assigned an address via the DIP switches The modules are assigned a consecutive address between 0 99 It is not necessary for the modules to be pla...

Page 8: ...1 0 0 Green blinking slowly 1 0 1 Green blinking rapidly 1 1 0 Green damper open 1 1 1 Red blinking slowly ADDRESSING The damper module is assigned an address via the DIP switches The modules are assi...

Page 9: ...linking slowly Reset smoke detector Blue blinking slowly Service detector Red blinking slowly Alarm ADDRESSING The module is assigned an address via the DIP switches It is not necessary for the module...

Page 10: ...to turn off acoustic alarm C 24 VDC supply Bus input LED indicators Status Yellow Ventilation fault alarm ADDRESSING Fault panel does not need to be given an adress fixed address 127 FUNCTION In case...

Page 11: ...ly PT1000 short circuited Red blinking slowly Alarm temperature or missing PT1000 ADDRESSING The damper module is assigned an address via the DIP switches The modules are assigned a consecutive addres...

Page 12: ...mps max 2 5 mm2 Dimensions 85x85x40 mm Temperature 0 50 C WIRING TERMINALS A 24 VDC input supply With 24VDC supply connected to all 4 relay outputs are activated extra terminal set for continuation of...

Reviews: