TX-INP1
9
TX-INP1 SPECIFICATIONS
AURASAFE mini input-module for
smokedetector/fire thermostat
Technical data
Inputs
Monitored input for fire alarm system /
smoke detector. 2K2 end resistor must be
mounted.
Addressing
DIP-switch
Indicator
LED on the side
Terminals
Springclamps, max. 2,5 mm
2
Dimensions
85x85x40 mm
WIRING TERMINALS
A. Fire alarm system / Smoke detector input
Up to two smoke detectors can be connected in a
series. 2,2 kohm resistance must be mounted on
the last smoke detector.
B. Supply/Bus input
2-wire bus supply. Two extra terminal-pairs for
forwarding.
C. Addressing DIP-switch
See separate description for addressing.
D. Reset-button
See separate description.
E. Cable fixation
F. LED indicator
See separate description for indicator.
LED indicators
Status
Green
OK
Green, blinking slowly
Reset smoke detector
Blue, blinking slowly
Service detector
Red, blinking slowly
Alarm
ADDRESSING
The module is assigned an address via the DIP switches. It is not
necessary for the modules to be placed in order during assembly.
If the module is connected to a fire alarm, choose an address
between 0 - 99. If it is connected to a smoke detector, choose an
adress between 100-119.
Each of the 7 switches represents a value, as indicated on the right.
The sum of the activated switches gives the module address. As
Example 1 shows, switches 1, 3 and 6 are activated. They each count
for 1 + 4 + 32, ie the module’s address becomes 37.
The same address must not be given to more than one damper.
MANUAL RESET OF SMOKE DETECTOR
By using the reset button it is possible to perform a manual reset of a
connected smoke detector. The button is held down until the LED
indicator starts blinking rapidly and the output is reset.
Value:
Example 2:
Address:
2 + 8 + 16 + 64 = 90
Example 1:
Address:
1 + 4 + 32 = 37