TX-TEM1

 11

TX-TEM1 SPECIFICATIONS

AURASAFE mini PT1000 Input module

Technical data

Inputs

 2 analogue inputs for PT1000
temperature sensors 

Addressing

DIP-switch

Indicator

LED on the side

Terminals

Springclamps, max. 2,5 mm

2

Dimensions

85x85x40 mm

Temperature

0-50 

˚

C

WIRING TERMINALS

A. 

PT1000 inputs 

 

PT1000 inputs if input is not used, 1 kohm/1% 

 

 

resistance must be mounted.

B.  Supply/Bus input

 

 

2-wire bus supply. Two extra terminal-pairs for 

 

forwarding.

C.  Addressing DIP-switch

 

 

See separate description for addressing.

D.  DIP-switch for alarm 

 

 

See separate description for addressing.

E.  Reset-button

 

 

See separate description.

F.  Cable fixation

G.  LED indicator

  

 

See separate description for indicator.

LED indicators

Status

Green

OK

Green, blinking slowly

Res

et module

Blue, blinking rapidly

PT1000 short-circuited

Red, blinking slowly

Alarm temperature or 

missing PT1000

ADDRESSING

The damper module is assigned an address via the DIP switches.

The modules are assigned a consecutive address between 0 - 99. It

is not necessary for the modules to be placed in order during

assembly.

Each of the 7 switches represents a value, as indicated on the right.

The sum of the activated switches gives the module address. As

Example 1 shows, switches 1, 3 and 6 are activated. They each count

for 1 + 4 + 32, ie the module’s address becomes 37.

The same address must not be given to more than one damper.

SETTING TEMPERATURE FOR ALARM

Use DIP-switch 8 to set the alarmlimit to 40 or 72 °C.

RESET AFTER ALARM

The module will blink green if there has been a temperature alarm or if

the input has had a short-circuit/been interrupted. The button is held

down until the LED light starts blinking rapidly and the module is reset. 

Value:

Example 2: 

 

Address:

2 + 8 + 16 + 64 = 90

Example 1: 

 

Address:

1 + 4 + 32 = 37

Summary of Contents for Auranor AURASAFE mini

Page 1: ...rs up to 100 fire dampers Digital error signal Connection to BMS by Modbus GB0351 02 22 AURASAFE mini Monitoring and control of fire dampers TROX Auranor Norge AS Auranorvegen 6 NO 2770 Jaren Phone 47...

Page 2: ...fe Mini 1 TX CTRL1 Controller std 12 Dampers 2 TX CTRL2 Controller lite 8 Dampers 3 TX BO1 Boostermodule 4 TX BRS3 Dampermodule for fire and smoke dampers 5 TX RKS1 Dampermodule for smoke control damp...

Page 3: ...and booster modules must have a 230V supply Figure 3 You can use the TX DREL1 Relay module to distribute the relay output of the AHU to 4 units TX INP1 Input module is used if smoke detector or fire...

Page 4: ...wire bus for supply and communication with bus modules E Alarm relay output F Smoke fan ventilated system relay output G Service relay output Indicates if service is required for smoke detectors H Ve...

Page 5: ...re bus for supply and communication with bus modules E Alarm relay output F Smoke fan ventilated system relay output G Service relay output Indicates if service is required for smoke detectors H Venti...

Page 6: ...Supply B Supply Bus output for damper modules Extended 2 wire bus for supply and communication with dampers C Bus input 2 wire bus input from existing network D LED indicators See separate description...

Page 7: ...1 Red blinking slowly ADDRESSING The damper module is assigned an address via the DIP switches The modules are assigned a consecutive address between 0 99 It is not necessary for the modules to be pla...

Page 8: ...1 0 0 Green blinking slowly 1 0 1 Green blinking rapidly 1 1 0 Green damper open 1 1 1 Red blinking slowly ADDRESSING The damper module is assigned an address via the DIP switches The modules are assi...

Page 9: ...linking slowly Reset smoke detector Blue blinking slowly Service detector Red blinking slowly Alarm ADDRESSING The module is assigned an address via the DIP switches It is not necessary for the module...

Page 10: ...to turn off acoustic alarm C 24 VDC supply Bus input LED indicators Status Yellow Ventilation fault alarm ADDRESSING Fault panel does not need to be given an adress fixed address 127 FUNCTION In case...

Page 11: ...ly PT1000 short circuited Red blinking slowly Alarm temperature or missing PT1000 ADDRESSING The damper module is assigned an address via the DIP switches The modules are assigned a consecutive addres...

Page 12: ...mps max 2 5 mm2 Dimensions 85x85x40 mm Temperature 0 50 C WIRING TERMINALS A 24 VDC input supply With 24VDC supply connected to all 4 relay outputs are activated extra terminal set for continuation of...

Reviews: