TX-CTRL1

TX-CTRL1 SPECIFICATIONS

AURASAFE mini Control Unit Standard for 12 firedampers

Technical data

Supply

230 VAC/80 VA

Bus voltage

24 VDC

Bus power

max. 48VA

Alarm relay output

3A/250 VAC, Normal-closed(NC)

Smoke ventilation relay output 3A/250 VAC, Normal-closed(NC)
Service relay output

3A/250 VAC, Normal-open(NO)

Ventilation relay output

3A/250 VAC, Normal-open(NO)

RS-485 port

Modbus 9600 baud, 1-stopbit, no parity

Dimensions

220x170x86 mm

WIRING TERMINALS

A.  230 VAC supply

B.  Input error signal frequency converter (ventilated system)

 

 

If not used, lask is retained.

C. 

Input for operating signal

 

 

External override signal, can be used for night function. All

 

 

dampers close if the input is not activated. If not used, lask is

 

 

retained.

D.  Supply/Bus output to dampermodules

 

 

2-wire bus for supply and communication with bus modules.

E.  Alarm relay output

F.  Smoke fan (ventilated system) relay output

G.  Service relay output

 

 

Indicates if service is required for smoke detectors

H. 

Ventilation relay output

I.  External alarm input

 

 

Signal from external unit (fire alarm system). 2.2 kohm resistor

 

 

must be connected in series. If the input is not used, 2.2 kohm 

 

 

resistor must be mounted.

J.  0-10 V input for pressure sensor (ventilated system)

  

 

24 VDC can be used to supply pressure transmitter. The 

 

 

pressure transmitter must have a measuring range of 0-300 Pa.

K.  Smoke detector input

 

 

Up to 10 smoke detectors can be connected in series. 

 

 

2.2 kohm resistor must be mounted on the last smoke detector. 

 

 

If the input is not used, 2.2 kohm resistor must be mounted.

L.  0-10 VDC output for frequency converter (ventilated  

 

system) 

Analog output for PID control of smoke fan.

M.  RS-485/Modbus port

 

 

Modbus interface

N. 

Fault panel output

O. 

Fuses for fault panel

 

 

2 x 250 mA , 20 x 5 mm

Summary of Contents for Auranor AURASAFE mini

Page 1: ...rs up to 100 fire dampers Digital error signal Connection to BMS by Modbus GB0351 02 22 AURASAFE mini Monitoring and control of fire dampers TROX Auranor Norge AS Auranorvegen 6 NO 2770 Jaren Phone 47...

Page 2: ...fe Mini 1 TX CTRL1 Controller std 12 Dampers 2 TX CTRL2 Controller lite 8 Dampers 3 TX BO1 Boostermodule 4 TX BRS3 Dampermodule for fire and smoke dampers 5 TX RKS1 Dampermodule for smoke control damp...

Page 3: ...and booster modules must have a 230V supply Figure 3 You can use the TX DREL1 Relay module to distribute the relay output of the AHU to 4 units TX INP1 Input module is used if smoke detector or fire...

Page 4: ...wire bus for supply and communication with bus modules E Alarm relay output F Smoke fan ventilated system relay output G Service relay output Indicates if service is required for smoke detectors H Ve...

Page 5: ...re bus for supply and communication with bus modules E Alarm relay output F Smoke fan ventilated system relay output G Service relay output Indicates if service is required for smoke detectors H Venti...

Page 6: ...Supply B Supply Bus output for damper modules Extended 2 wire bus for supply and communication with dampers C Bus input 2 wire bus input from existing network D LED indicators See separate description...

Page 7: ...1 Red blinking slowly ADDRESSING The damper module is assigned an address via the DIP switches The modules are assigned a consecutive address between 0 99 It is not necessary for the modules to be pla...

Page 8: ...1 0 0 Green blinking slowly 1 0 1 Green blinking rapidly 1 1 0 Green damper open 1 1 1 Red blinking slowly ADDRESSING The damper module is assigned an address via the DIP switches The modules are assi...

Page 9: ...linking slowly Reset smoke detector Blue blinking slowly Service detector Red blinking slowly Alarm ADDRESSING The module is assigned an address via the DIP switches It is not necessary for the module...

Page 10: ...to turn off acoustic alarm C 24 VDC supply Bus input LED indicators Status Yellow Ventilation fault alarm ADDRESSING Fault panel does not need to be given an adress fixed address 127 FUNCTION In case...

Page 11: ...ly PT1000 short circuited Red blinking slowly Alarm temperature or missing PT1000 ADDRESSING The damper module is assigned an address via the DIP switches The modules are assigned a consecutive addres...

Page 12: ...mps max 2 5 mm2 Dimensions 85x85x40 mm Temperature 0 50 C WIRING TERMINALS A 24 VDC input supply With 24VDC supply connected to all 4 relay outputs are activated extra terminal set for continuation of...

Reviews: