AURASAFE mini

 APPLICATION

AURASAFE mini is a control- and monitoringsystem for firedampers.

It can monitor and control up to 100 fire dampers, by combining the

control unit with booster modules. The system is suitable for small

and medium-sized facilities where there is no need for multiple fire

scenarios to be taken into account. AURASAFE mini is equipped

with a relay output for stopping fans, input for fire alarm, digital error

signal and Modbus communication for BMS systems.

      

 FUNCTION

AURASAFE Mini communicates with damper module TX-BRS3 via

flexibus. A 2-wire cable with free topology is used, and this contains

both bus-communication and 24V operating voltage for fire dampers.

A TX-BRS3 is set up for each fire damper in the facility. AURASAFE

Mini controls the fire dampers based on received signals, and

exercise of dampers can be done automatically, manually via control

panel, or by signal from BMS system. You can read about how to set

up the master at our website: www.trox.no

 DESIGN

The AURASAFE Mini controller is encapsulated in an IP65 box. The

other components of the system are also encapsulated in plastic

boxes.

 ORDER CODE, 

AURASAFE mini

AuraSafe Mini 

 

09.02.21 

Order code:  

 

 

 

Product: 

Komponenter: 

Aurasafe Mini - 

 

1 = 

TX-CTRL1 Controller std 12 Dampers 

2 = 

TX-CTRL2 Controller lite 8 Dampers 

3 = 

TX-BO1 Boostermodule 

4 = 

TX-BRS3 Dampermodule for fire- and smoke dampers 

5 = 

TX-RKS1 Dampermodule for smoke control dampers 

6 = 

TX-INP1 Inputmodule for smoke detector/fire thermostat 

7 = 

TX-FEP1 Faultpanel 

8 = 

TX-TEM1 PT1000 Inputmodule 

9 = 

TX-DREL1 Relaymodule 4DO 

 

 INSTALLATION

Mechanical installation

AURASAFE mini is attached directly to the wall with four screws.

 MAINTENANCE

There are no special maintenance requirements.  

 

ENVIRONMENT

 

Inquiries regarding product declarations can be directed to one of

our sales reps or can be found on our website : www.trox.no

 MATERIALS AND SURFACE COATING

The control cabinet and modules are made of plastic.

Table 1

Technical data

Power supply

AC 230 V, 50/60 Hz

Connection

Clamps, max 250 VAC.

Cable diameter 0,5….2,5 mm²

Communication with
damper

Up to 12 dampers can be connected together in

a section of 100 m, 1.5 mm, 2 2-wire cable

Figure 1, Shows a typical layout. From the control panel to damper modules, 2-wire cable is used for bus communication and 24V for

fire dampers (no need for shielded cable). This can be wired in series, in star or in ring. Optional topology. When using 1.5 mm² you can

have approx. 100 cable lengths (from control panel to farthest damper). Use the cable calculator at www.trox.no for exact calculation. 

 

A 3-wire cable is used for the fault panel.

Faultpanel

Controller

Total 12 pcs

Summary of Contents for Auranor AURASAFE mini

Page 1: ...rs up to 100 fire dampers Digital error signal Connection to BMS by Modbus GB0351 02 22 AURASAFE mini Monitoring and control of fire dampers TROX Auranor Norge AS Auranorvegen 6 NO 2770 Jaren Phone 47...

Page 2: ...fe Mini 1 TX CTRL1 Controller std 12 Dampers 2 TX CTRL2 Controller lite 8 Dampers 3 TX BO1 Boostermodule 4 TX BRS3 Dampermodule for fire and smoke dampers 5 TX RKS1 Dampermodule for smoke control damp...

Page 3: ...and booster modules must have a 230V supply Figure 3 You can use the TX DREL1 Relay module to distribute the relay output of the AHU to 4 units TX INP1 Input module is used if smoke detector or fire...

Page 4: ...wire bus for supply and communication with bus modules E Alarm relay output F Smoke fan ventilated system relay output G Service relay output Indicates if service is required for smoke detectors H Ve...

Page 5: ...re bus for supply and communication with bus modules E Alarm relay output F Smoke fan ventilated system relay output G Service relay output Indicates if service is required for smoke detectors H Venti...

Page 6: ...Supply B Supply Bus output for damper modules Extended 2 wire bus for supply and communication with dampers C Bus input 2 wire bus input from existing network D LED indicators See separate description...

Page 7: ...1 Red blinking slowly ADDRESSING The damper module is assigned an address via the DIP switches The modules are assigned a consecutive address between 0 99 It is not necessary for the modules to be pla...

Page 8: ...1 0 0 Green blinking slowly 1 0 1 Green blinking rapidly 1 1 0 Green damper open 1 1 1 Red blinking slowly ADDRESSING The damper module is assigned an address via the DIP switches The modules are assi...

Page 9: ...linking slowly Reset smoke detector Blue blinking slowly Service detector Red blinking slowly Alarm ADDRESSING The module is assigned an address via the DIP switches It is not necessary for the module...

Page 10: ...to turn off acoustic alarm C 24 VDC supply Bus input LED indicators Status Yellow Ventilation fault alarm ADDRESSING Fault panel does not need to be given an adress fixed address 127 FUNCTION In case...

Page 11: ...ly PT1000 short circuited Red blinking slowly Alarm temperature or missing PT1000 ADDRESSING The damper module is assigned an address via the DIP switches The modules are assigned a consecutive addres...

Page 12: ...mps max 2 5 mm2 Dimensions 85x85x40 mm Temperature 0 50 C WIRING TERMINALS A 24 VDC input supply With 24VDC supply connected to all 4 relay outputs are activated extra terminal set for continuation of...