Operating manual – dehumidifier TTK 110 HEPA

Automatic defrost

At low ambient temperatures, ice may form at the evaporator
during dehumidification. The device will then carry out an
automatic defrost. Dehumidification is briefly interrupted during
defrosting.
The duration of the defrost process can vary. Do not switch off
the device during automatic defrost. Do not remove the mains
plug from the mains socket.
The 

low ambient temperature

 indication (31) flashes during

defrosting.

Drying laundry

In addition, the device may also be used as a kind of clothes
dryer to dry wet laundry.
For drying laundry the following values should be selected:

cupboard dry = 46 % relative humidity

iron dry = 58 % relative humidity

slightly dried = 65 % relative humidity

If necessary, use a measuring device to determine the humidity
level.

Shutdown

Warning of electrical voltage

Do not touch the mains plug with wet or damp hands.

Switch off the device.

Hold onto the mains plug while pulling the power cable out
of the mains socket.

If necessary, remove the condensation drain hose and any
residual fluid from it.

Empty the condensation tank, if need be.

If necessary, carry out self-cleaning (see Self-cleaning
function).

Clean the device according to the Maintenance chapter.

Store the device according to the Storage chapter.

Available accessories

Warning

Only use accessories and additional equipment
specified in the operating manual.
Using insertion tools or accessories other than those
specified in the operating manual may cause a risk of
injury.

Accessories

Article number

HEPA filter

7.710.000.835

Carbon filter

7.710.000.836

Errors and faults

The device has been checked for proper functioning several
times during production. If malfunctions occur nonetheless,
check the device according to the following list.

The device does not start:

Check the power connection.

Check the power cable and mains plug for damages.

Check the on-site fusing.

Check the filling level of the condensation tank and empty
it if necessary. The 

condensation tank full

 indication (11)

must not be displayed.

Check the condensation tank for correct seating.

Check whether the 

low ambient temperature

indication (31) flashes on the display. Possibly, the device
does not start because the ambient temperature is too low
(< 5 °C).

Wait for 10 minutes before restarting the device. If the
device is not starting, have the electrics checked by a
specialist company or by Trotec.

The device is running, but no condensate forms:

Check the float in the condensation tank for dirt. If
necessary, clean the condensation tank. The float must be
able to move freely.

Check the room temperature. Observe the device's
permissible operating range according to the technical
data.

Ensure that the relative room humidity complies with the
technical data.

Check the preselected desired room humidity level. The
relative humidity in the room must be above the selected
range. If necessary, reduce the preselected desired room
humidity.

Check the air filter for dirt. If necessary, clean or replace
the air filter.

Check whether the 

low ambient temperature

indication (31) flashes on the display. Possibly, the device
does not start because the ambient temperature is too low
(< 5 °C).

From the outside, check the condenser for dirt (see
chapter Maintenance). If the condenser is dirty, have it
cleaned by a specialist company or by Trotec.

The device might carry out an automatic defrost. During
automatic defrost, the device does not dehumidify.

The device is loud or vibrates:

Check whether the device is set up in a stable and upright
position.

Condensate is leaking:

Check the device for leaks.

Summary of Contents for TTK 110 HEPA

Page 1: ...TRT BA TTK110HEPA TC 002 EN TTK 110 HEPA EN OPERATING MANUAL DEHUMIDIFIER...

Page 2: ...r using the device Always store the manual in the immediate vicinity of the device or its site of use Warning Read all safety warnings and all instructions Failure to follow the warnings and instructi...

Page 3: ...Ensure that the side of the device where the air inlet is found is kept free of dirt and loose objects Only transport the device in an upright position with an emptied condensation tank or drain hose...

Page 4: ...air can be additionally improved Another feature is the device s self cleaning function This function serves to dry the interior of the device in order to prevent the formation of mould or similar in...

Page 5: ...he following Set up the device in an upright position after transport Leave the device to rest for 12 24 hours so the refrigerant can accumulate within the compressor Wait 12 24 hours before switching...

Page 6: ...ectric cables especially when positioning the device in the middle of the room Use cable bridges Make sure that extension cables are completely unrolled When positioning the device keep a sufficient d...

Page 7: ...rent room temperature Indicates the number of hours of the activated timer ON is displayed if the timer for automatic switch on is active OFF is displayed if the timer for automatic switch off is acti...

Page 8: ...d The fan speed cannot be changed The compressor switches off automatically once the desired relative room humidity has been reached The fan keeps running 1 Press the MODE button 23 until the indicati...

Page 9: ...button 23 until the indication for the ventilation indication 19 appears on the display 2 Press the HUMIDITY button 34 to select low or high fan speed Night mode Night mode can be switched on in all o...

Page 10: ...setting The characters OFF and the number of hours left until switch off appear on the temperature and timer indication 18 The timer setting equals the desired number of hours The device switches off...

Page 11: ...ses when released 37 36 5 With the other hand push one end of the hose onto the hose connection 37 37 6 Let go of the fastener 36 7 Refit the condensation tank into the device Make sure not to damage...

Page 12: ...production If malfunctions occur nonetheless check the device according to the following list The device does not start Check the power connection Check the power cable and mains plug for damages Che...

Page 13: ...mode If the device is in air purification mode and the HEPA filter is not inserted the fan will not start Insert the HEPA filter in air purification mode see Replacing the HEPA filter The device gets...

Page 14: ...drain hose X Check the air inlets and outlets for dirt and foreign objects and clean if necessary X X Clean the exterior X X Visually check the inside of the device for dirt X X Check the air filter f...

Page 15: ...irt Check the air filter for dirt and foreign objects and clean or replace if necessary Replace the air filter Check the HEPA filter for dirt and foreign objects and clean or replace if necessary Repl...

Page 16: ...de of the device cleaned by a specialist company for cooling and air conditioning or by Trotec 5 Put the air filter back in Refrigerant circuit The entire refrigerant circuit is a maintenance free her...

Page 17: ...that it is undamaged and dry The air filter has to be cleaned as soon as it is dirty This is brought to light e g by a reduced capacity see chapter Errors and faults 1 Remove the air filter from the...

Page 18: ...ondensation tank In doing so make sure that the float is positioned correctly In doing so make sure that the condensation tank is inserted correctly for otherwise the device cannot be switched back on...

Page 19: ...Sensor BN BU YE GN GN YE GN GN RD Capacitor BU BU BN RD BK RD BK WH BU BU BN WH BK ELECTRIC CIRCUIT DIAGRAM YDH CN1 CN9 PH CN4 CN5 PG Water RT1 RD WH BU Photodiode Photodiode Disposal The icon with t...

Page 20: ...Trotec GmbH Co KG Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com...

Reviews: