background image

EN

3

dehumidifier TTK 100 E

Ensure that all electric cables outside of the device are
protected from damage (e.g. caused by animals). Never
use the device if electric cables or the power connection
are damaged!

The mains connection must correspond to the
specifications in the Technical annex.

Insert the mains plug into a properly fused mains socket.

Observe the device's power input, cable length and
intended use when selecting extensions to the power
cable. Completely unroll extension cables. Avoid electrical
overload.

Before carrying out maintenance, care or repair work on
the device, remove the mains plug from the mains socket.
Hold onto the mains plug while doing so.

Switch the device off and disconnect the power cable from
the mains socket when the device is not in use.

Do not under any circumstances use the device if you
detect damages on the mains plug or power cable. 
If the power cable is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
Defective power cables pose a serious health risk!

When positioning the device, observe the minimum
distances from walls and other objects as well as the
storage and operating conditions specified in the Technical
annex.

Make sure that the air inlet and outlet are not obstructed.

Make sure that the suction side is kept free of dirt and
loose objects.

Do not remove any safety signs, stickers or labels from the
device. Keep all safety signs, stickers and labels in legible
condition.

Only transport the device in an upright position with an
emptied condensation tank or drain hose.

Discharge the collected condensate before transport and
storage. Do not drink it. Health hazard!

Safety warnings for devices containing flammable
refrigerants

Only position the device in rooms where potentially leaking
refrigerant cannot accumulate.

Only position the device in rooms where there is no source
of ignition (e.g. open flames, an active gas appliance or an
electric heater).

Please note that the refrigerant is odourless.

Only install the device in compliance with the national
installation regulations.

Observe the national gas regulations.

Only install, operate and store the device 

TTK 100 E

 in a

room measuring more than 4 m

2

.

Store the device in a way that no mechanical damage can
occur.

Please note that the connected pipelines must not contain
any sources of ignition.

R290 is a refrigerant that complies with European
environmental regulations. No part of the cooling circuit
may be perforated.

Observe the maximum refrigerant capacity in the technical
data.

Do not drill through or burn.

Do not use any means other than those recommended by
the manufacturer for accelerating the defrosting process.

Every person working with or at the refrigerant circuit must
be able to provide a certificate of qualification issued by a
body accredited by the industry, demonstrating their
competence in the safe use of refrigerants based on a
procedure well-known in the industry.

Service work may only be carried out in accordance with
the manufacturer's specifications. If maintenance and
repair work require the support of additional persons, the
person trained in handling flammable refrigerants shall
continuously supervise the work carried out.

Unventilated rooms, in which the device is installed,
operated or stored, must be built in a way to ensure that
potentially leaking refrigerant cannot accumulate. This
serves to avoid fire or explosion hazards resulting from an
ignition of the refrigerant by an electric furnace, cooking
stove or another ignition source.

The entire refrigerant circuit is a maintenance-free,
hermetically sealed system and may only be maintained or
repaired by specialist companies for cooling and air-
conditioning or by Trotec.

Summary of Contents for TTK 100 E

Page 1: ...TRT BA TTK100E TC2019 35 010 EN TTK 100 E EN OPERATING MANUAL DEHUMIDIFIER...

Page 2: ...r using the device Always store the manual in the immediate vicinity of the device or its site of use Warning Read all safety warnings and all instructions Failure to follow the warnings and instructi...

Page 3: ...device in rooms where potentially leaking refrigerant cannot accumulate Only position the device in rooms where there is no source of ignition e g open flames an active gas appliance or an electric he...

Page 4: ...ad and understood the operating manual especially the Safety chapter Maintenance tasks which require the housing to be opened must only be carried out by specialist companies for cooling and air condi...

Page 5: ...r inlet the air filter the evaporator and to the condenser located behind it The air is cooled at the cold evaporator until it is below the dew point Water vapour contained in the room air precipitate...

Page 6: ...the device and the condensation drain hose see chapter Maintenance Do not use the power cable to drag the device Only wheel the device on a level and smooth surface After transporting the device proc...

Page 7: ...ground Do not create tripping hazards when laying the power cable or other electric cables especially when positioning the device in the middle of the room Use cable bridges Make sure that extension...

Page 8: ...ents of 10 13 Arrow button up 14 Speed button For setting a high or low fan speed Display 20 21 19 18 17 16 15 No Designation Meaning 15 Condensation tank full indication Is displayed when the condens...

Page 9: ...er of hours can be set in hourly increments 1 h to max 12 h Automatic switch on The device is now in standby mode 1 Repeatedly press the timer button 11 until the desired number of hours is displayed...

Page 10: ...n through the condensation tank opening 5 Put the condensation tank back in 6 Guide the other hose end to a suitable drain or sufficiently dimensioned collection container Please note that the hose mu...

Page 11: ...residual fluid from it Empty the condensation tank if need be Clean the device according to the Maintenance chapter Store the device according to the Transport and storage chapter Errors and faults Th...

Page 12: ...r maintenance and repair work Only then switch the device back on The device still does not operate correctly after these checks Please contact the customer service If necessary bring the device to a...

Page 13: ...or drain hose X Maintenance and care log Device type Device number Maintenance and care interval 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Check air inlets and outlets for dirt and foreign objects and c...

Page 14: ...abels on the device Check the safety signs and labels attached to the device at regular intervals Replace illegible safety signs Cleaning the housing Clean the housing with a soft damp and lint free c...

Page 15: ...letely Do not insert a wet filter into the device 5 Put the air filter back in 6 Reinsert the flap into the device Emptying the condensation tank If the condensation tank is full or not inserted corre...

Page 16: ...essor damage and a malfunctioning device If so any warranty claims will be voided Reconnect the device to the mains If you do not intend to use the device for a considerable time Store the device acco...

Page 17: ...EN 17 dehumidifier TTK 100 E Wiring diagram...

Page 18: ...18 EN dehumidifier TTK 100 E Overview and list of spare parts Note The position numbers of the spare parts differ from those describing the positions of other parts mentioned in this operating manual...

Page 19: ...rical or electronic equipment stipulates that this equipment must not be disposed of with the household waste at the end of its life You will find collection points for free return of waste electrical...

Page 20: ...Trotec GmbH Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com...

Reviews: