12

EN

dehumidifier TTK 100 E

The compressor does not start:

Check the room temperature. Observe the device's
permissible operating range according to the technical
data.

Ensure that the relative room humidity complies with the
technical data.

Check the preselected relative room humidity. The
humidity in the room must be above the selected range.

Check whether the overheating protection of the
compressor has tripped. Disconnect the device from the
mains and let it cool down for approx. 10 minutes before
reconnecting it.

The device might carry out an automatic defrost. During
automatic defrost, the device does not dehumidify.

The device gets very warm, is loud or is losing
performance:

Check the air inlets and air filters for dirt. Remove external
dirt.

From the outside, check the device for dirt (see chapter
Maintenance). If the inside of the device is dirty, have it
cleaned by a specialist company for cooling and air-
conditioning or by Trotec.

Note

Wait for at least 3 minutes after maintenance and
repair work. Only then switch the device back on.

The device still does not operate correctly after these
checks:

Please contact the customer service. If necessary, bring the
device to a specialist company for cooling and air-conditioning
or to Trotec for repair.

Error codes

The following error messages can be displayed on the segment
display:

Error code Cause

Remedy

E1

Temperature
sensor – circuit
interrupted / short
circuit

Switch off the device and
call the customer service.

E2

Defrost sensor –
circuit interrupted /
short circuit

Switch off the device and
call the customer service.

E3

Humidity sensor –
circuit interrupted /
short circuit

Switch off the device and
call the customer service.

Lo

The current humidity
level is lower than
30 % RH.

Activate the dehumidifier at
a humidity level which
complies with the technical
data. 
Should the alarm persist,
please contact the
customer service.

Hi

The current humidity
level is higher than
90 % RH.

Activate the dehumidifier at
a humidity level which
complies with the technical
data. 
Should the alarm persist,
please contact the
customer service.

E5

Chip communication
failure

Switch off the device and
call the customer service.

Summary of Contents for TTK 100 E

Page 1: ...TRT BA TTK100E TC2019 35 010 EN TTK 100 E EN OPERATING MANUAL DEHUMIDIFIER...

Page 2: ...r using the device Always store the manual in the immediate vicinity of the device or its site of use Warning Read all safety warnings and all instructions Failure to follow the warnings and instructi...

Page 3: ...device in rooms where potentially leaking refrigerant cannot accumulate Only position the device in rooms where there is no source of ignition e g open flames an active gas appliance or an electric he...

Page 4: ...ad and understood the operating manual especially the Safety chapter Maintenance tasks which require the housing to be opened must only be carried out by specialist companies for cooling and air condi...

Page 5: ...r inlet the air filter the evaporator and to the condenser located behind it The air is cooled at the cold evaporator until it is below the dew point Water vapour contained in the room air precipitate...

Page 6: ...the device and the condensation drain hose see chapter Maintenance Do not use the power cable to drag the device Only wheel the device on a level and smooth surface After transporting the device proc...

Page 7: ...ground Do not create tripping hazards when laying the power cable or other electric cables especially when positioning the device in the middle of the room Use cable bridges Make sure that extension...

Page 8: ...ents of 10 13 Arrow button up 14 Speed button For setting a high or low fan speed Display 20 21 19 18 17 16 15 No Designation Meaning 15 Condensation tank full indication Is displayed when the condens...

Page 9: ...er of hours can be set in hourly increments 1 h to max 12 h Automatic switch on The device is now in standby mode 1 Repeatedly press the timer button 11 until the desired number of hours is displayed...

Page 10: ...n through the condensation tank opening 5 Put the condensation tank back in 6 Guide the other hose end to a suitable drain or sufficiently dimensioned collection container Please note that the hose mu...

Page 11: ...residual fluid from it Empty the condensation tank if need be Clean the device according to the Maintenance chapter Store the device according to the Transport and storage chapter Errors and faults Th...

Page 12: ...r maintenance and repair work Only then switch the device back on The device still does not operate correctly after these checks Please contact the customer service If necessary bring the device to a...

Page 13: ...or drain hose X Maintenance and care log Device type Device number Maintenance and care interval 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Check air inlets and outlets for dirt and foreign objects and c...

Page 14: ...abels on the device Check the safety signs and labels attached to the device at regular intervals Replace illegible safety signs Cleaning the housing Clean the housing with a soft damp and lint free c...

Page 15: ...letely Do not insert a wet filter into the device 5 Put the air filter back in 6 Reinsert the flap into the device Emptying the condensation tank If the condensation tank is full or not inserted corre...

Page 16: ...essor damage and a malfunctioning device If so any warranty claims will be voided Reconnect the device to the mains If you do not intend to use the device for a considerable time Store the device acco...

Page 17: ...EN 17 dehumidifier TTK 100 E Wiring diagram...

Page 18: ...18 EN dehumidifier TTK 100 E Overview and list of spare parts Note The position numbers of the spare parts differ from those describing the positions of other parts mentioned in this operating manual...

Page 19: ...rical or electronic equipment stipulates that this equipment must not be disposed of with the household waste at the end of its life You will find collection points for free return of waste electrical...

Page 20: ...Trotec GmbH Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com...

Reviews: