Installation Guide ROQSTAR
Document no. 130-103.44 11/2016 ENG
Seite 10 von 16
5.2.
Ethernet port LEDs
Each network port is assigned two LEDs. Their meaning is given in the table below.
LED
Colour
Activity
Operational State
Link
-
none
no network connection, Link-Down
green
lights up
network connection, Link-Up
Act
-
none
no data transfer
yellow
flashes
data transfer with 10/100 MBit / s
6.
Technical data
6.1.
Electrical
Parameter
min.
typ.
max.
Dim.
Operating voltage (V1, V2) SELV
+9,6
+24
+60
VDC
Reset level (V1, V2)
-
8,0
-
VDC
Current consumption, full load all ports
V1,V2 = 9.6V
V1,V2 = 24V
V1,V2 = 60V
-
-
-
380
161
79
418
186
88
mA
mA
mA
Peak inrush current
<1ms
-
10 @ 9,6V
14 @ 60V
A
Input
V1,V2 = 9.6V
V1,V2 = 24V
V1,V2 = 60V
-
-
-
3,6
3,9
4,7
4,0
4,5
5,3
W
W
W
Bridging of power outage
10
-
-
ms
Internal fuse
2A, T
-
Ethernet-Ports
min.
typ.
max.
Dimension
Switch architecture
Store-and-Forward
Bitrate
-
10 / 100
-
Mbit/s
Output resistance
-
100
-
Input resistance
-
100
-
Latency at 90 % load
at 100 Mbit/s (frame size 64 / 1518 Byte)
at 10 Mbit/s (frame size 64 / 1518 Byte)
-
-
8 / 125
8 / 125
9 / 133
9 / 133
µs
µs
Throughput unicast packets
Frame size 64
– 1518 Byte
-
Full wire
speed
-
Frame size
without VLAN Tag
with VLAN Tag
64
64
-
1518
1522
Byte
Byte