TROUBLESHOOTING:
Symptom
Cause
Corrective Action
No voltage reading on meter
when connected to battery, and
the LED flashes red/green.
Connected reverse to battery,
or not connected to battery.
Break in DC cord, or
connector.
Battery too dead to charge.
Correct polarity, or connect to
battery. On chargers having a
white and black wire, white is
positive.
Have a qualified person make
repair.
Replace.
When switched on, the red LED
does not light, and no amps read
on meter
The panel mount fuse is
blown.
There is no AC power present
at the plug.
Replace with one having the same
rating.
Check that there is power at the
source. If using an extension cord,
check that it is not damaged.
When I put a volt meter across
the output of the charger there is
no power coming out when I
switch it on.
The charger must be
connected to a battery to turn
on.
The batteries don’t receive a full
charge. On wet cells, the
specific gravity will not rise to a
full reading after the charge has
completed.
The charger is too small for
the battery.
The charge profile is not set
correctly.
The cycle needs more time.
The battery is defective.
Check that the charger’s output is
about 10% of the amp hour rating
of the battery.
Recheck the dip switch setting. If
in doubt, contact us.
If you have a 4 position switch,
switch #1 position ON.
Replace.
The battery voltage reads well
below the rating of the battery,
and when powered up the LED
is red with a yellow flash, and
the amps are less than 5.
The battery is very low, and
the charger is in a slow charge
phase until the voltage rises to
a safe level before full turn on.
Leave connected, it may take
hours, but if the voltage rises even
a little bit, it should recover, and
turn the charger full on. (
Do not
allow your batteries to deep
discharge, it is the number one
cause of premature battery
failure
.)
When switched on, the LED
flashes red/yellow, and there is
no amp output on the meter
Charger and battery voltage
mismatch
Connect the charger to a battery(s)
with the same voltage rating.
The charger blows it’s fuse, or
branch circuit fuse/circuit
breaker as soon as it’s switched
on.
Charger is shorted
Contact factory.
Summary of Contents for JP30
Page 32: ...Models JP30 JP30L Electric Towbarless Tug 07 2015 Rev 10 Page 28 Axle Assembly...
Page 49: ...APPENDIX I INS 1857 Hydraulic Schematic...
Page 50: ......
Page 51: ...APPENDIX II INS 2276 Electrical Schematic...
Page 52: ......
Page 53: ...APPENDIX III INS 2277 INS 2278 Wiring Diagrams...
Page 54: ......
Page 55: ...APPENDIX IV Deep Cycle Battery Handling Maintenance and Test Procedures...
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ...APPENDIX V Battery Charger Operating Instructions Warranty...
Page 66: ......
Page 76: ......
Page 77: ...APPENDIX VI Honeywell Battery and Time Controller Operating Instructions...
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ...APPENDIX VII Declaration Of Conformity...
Page 82: ......