background image

IVORY 4 electric shower

7

Shower unit

must not

be within

an area

1 metre

from base

Height of 

showerhead

and shower 

to suit user's

requirement

Spillover

level

25 mm minimum

Shower unit can

be mounted either

side of riser rail

Outline of bath

or shower tray

W-008-A

WARNING!

The shower must not be positioned 

where it will be subjected to freezing 

conditions.

I-002-A

IMPORTANT: 

The unit must be mounted on 

a  flat  surface  which  covers  the  full  width 
and length of the backplate. It is important 
that  the  wall  surface  is  flat  otherwise 
difficulty may be encountered when fitting 
the cover and subsequent operation of the 
unit may be impaired.

SITING OF THE SHOWER

IMPORTANT:

 If installing onto a tiled wall 

always mount the unit on the surface of the 
tiles. NEVER tile up to the unit.

Refer to 

(fig.6)

 for the correct siting of the 

shower. Position the unit where it will NOT

 

be in 

direct contact with water from the showerhead. 
Position the shower unit vertically.
Allow enough room between the ceiling and the 
shower to access the cover top screws. Leave 
enough space between the right-hand side of the 
unit and the wall to allow access to the pressure 
relief device (PRD) in the future.

Note:

 Water regulations require the showerhead 

be ‘constrained by a fixed or sliding attachment 
so that it can only discharge water at a point not 
less than 25mm above the spill-over level of the 
relevant bath, shower tray or other fixed appliance’. 
The use of the gel hanger/hose guide (if supplied) 
will in most cases meet this requirement, but if the 
showerhead can be placed within a bath, basin or 
shower tray, then a double check valve, or similar, 

MUST

 be fitted in the supply pipework to prevent 

back-flow.

Pressure relief device - PRD

A pressure relief device (PRD) is designed into 
the shower unit which complies with European 
standards. The PRD provides a level of appliance 
protection should an excessive build up of pres-
sure occur within the shower.

Do not operate the shower with a damaged or 
kinked shower hose, or a blocked showerhead 
which can cause the PRD to operate.

When commissioning, the showerhead must 
be removed from the flexible hose, while at the 
same time the temperature control must be at 
the minimum flow position. Failure to follow this 
procedure may also cause the PRD to operate.
Make sure the shower is positioned over a bath 
or shower tray because if the PRD operates, then 
water will eject from the bottom of the unit.
Should this happen, turn off the electricity and 
water supplies to the shower at the isolating 
switch and stopvalve. Contact Customer Service 
for advice on replacing the PRD.

*Fig.6

*

(diagrammatic view – not to scale)

Summary of Contents for IVORY 4

Page 1: ...Installers please note these instructions are to be left with the user 2180775H April 2012 Installation and operating instructions IVORY 4 electric shower...

Page 2: ...ing connections 11 Electrical connections 12 Replacing the cover 12 13 Commissioning 14 Operating the shower 15 16 Operating functions 17 Cleaning 17 Instructions for installers and service engineers...

Page 3: ...and could also cause the PRD Pressure Relief Device in the unit to operate 1 9 This product is not suitable for mounting into steam rooms or steam cubicles 2 PLUMBING 2 1 The plumbing installation mus...

Page 4: ...rate at a constant rate at your chosen power setting It is the rate of the water passing through the heater can which determines the water temperature The slower the flow the hotter the water becomes...

Page 5: ...ising valve 6 Solenoid valve 7 Can and element assembly 8 Thermal cut out TCO 9 Earth connection 10 Outlet pipe 11 Start Stop micro switch Pressure relief device see page 20 Cover fig 2 12 Ivory 4 fro...

Page 6: ...bt switch off the whole installation at the mains supply and remove the correct fuse 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a ring main sp...

Page 7: ...dy while standing in a bath or shower cubicle It should be readily accessible to switch off after using the shower 7 Where shower cubicles are located in any rooms other than bathrooms all socket outl...

Page 8: ...es per minute the inlet of the shower for full performance for 7 5Kw 8 5Kw 9 5Kw Minimum running pressure and flow to 150kPa 1 5 bar at 11 litres per minute the inlet of the shower for full performanc...

Page 9: ...showerhead be constrained by a fixed or sliding attachment so that it can only discharge water at a point not less than 25mm above the spill over level of the relevant bath shower tray or other fixed...

Page 10: ...t to remove them Lift the cover from the backplate Entry Points Water Left Bottom Back and Top Right Bottom Back Cable Left Bottom Back and Top The water inlet fig 7 has been designed to allow left or...

Page 11: ...ide if top or bottom pipe entry is required Once chosen carefully remove the appropriate cut out using a junior hacksaw and file Please note NONE of the cut outs are designed as snap out entry points...

Page 12: ...the backplate are shown in fig 10 Drill and plug the wall An appropriate drill bit should be used If the wall is brick plasterboard or a soft building block appropriate wall plugs and screws should b...

Page 13: ...the shower flush out the pipework to remove all swarf and system debris This can be achieved by connecting a hose to the pipework and turning on the mains water supply long enough to clear the debris...

Page 14: ...ply cable must be secured either by rout ing through conduit or in trunking or by embed ding in the wall in accordance with current IEE regulations The use of connections within the unit to supply pow...

Page 15: ...turn the stabi liser valve spindle fully clockwise until resistance is felt fig 14 4 With the cover off the shower turn the tem perature control so that it goes to Maximum HOT fig 16 c Make sure the...

Page 16: ...he control to MINIMUM FLOW may cause the PRD to operate 2 Turn on the electric and mains water supplies to the shower 3 Turn the power selector to the COLD setting fig 18 and wait until water starts t...

Page 17: ...ot be met due to low water pressure it will be necessary to operate the unit on this setting during the warmer months because of flow rate limitations entering the unit The symbol is a high power sett...

Page 18: ...s advisable to be certain that the showering temperature is satisfactory by testing with your hand before stepping under the showerhead There will always be a time delay of a few seconds between selec...

Page 19: ...will disconnect the heating elements It will require a visit from a qualified engineer to determine the nature of the fault and replace the safety device once the unit has been repaired TP Temperatur...

Page 20: ...electricity supply and water supply at the mains The inlet filter is situated in the bottom of the inlet pipe fig 20 To gain access to the filter remove the cover and then unscrew the assembly from t...

Page 21: ...ch Module P22611003 5 Can Assembly 8 5kW 83314800 Can Assembly 9 5kW 83314810 Can Assembly 10 5kW 83314820 6 Outlet Pipe and PRD S23511002 7 Terminal Block wires S82201240 8 Thermal Cut Out TCO 220123...

Page 22: ...educe flow rate via temperature control Is water supply mains or tank fed If tank fed replumb to mains water supply or see 4 2 4 If mains fed make sure that the mains stopvalve is fully open and there...

Page 23: ...4 2 4 4 3 1 4 3 2 4 4 1 5 1 1 6 1 1 6 2 1 6 3 1 6 4 1 7 1 1 7 2 1 7 3 1 required see rating label Reduction in ambient water temperature Electrical malfunction or safety cut out operated Water pressu...

Page 24: ...IVORY 4 electric shower 22 Entry Points Diagram Key Water Entry Points Cable Entry Points...

Page 25: ...IVORY 4 electric shower 23...

Page 26: ...IVORY 4 electric shower 24...

Page 27: ...nt Agency under the following schemes Repic Producers take back scheme PTS registration number WEE EJ3466QV Valpak Distributor take back scheme DTS registration number 9659 All our electric products a...

Page 28: ...your details including post code the model number and power rating of the product together with the date of purchase and where applicable details of the particular fault 2 If required the Customer Se...

Reviews: