32
11. Troubleshooting
11.1 Troubleshooting Table
Problem
Possible Cause
Solution
No power displayed on
panel or any one of the
buttons failure
Power failure
Check if the power supplier is supplying power to the unit. Check
the power cord and correct if damaged.
Transformer (discharge
transformer before testing)
Check resistance between the two input/output lines on
transformer. Replace the transformer if either the input/output is
open or the transformer is damaged.
Display board or main PCB
failure
Check the voltage on the display board. Replace the display
board if it is +5V. Otherwise, replace the main PCB.
Remote control failure
Battery failure
Check the battery voltage. Replace batteries if the voltage is
lower than 2.3V.
Fan motor runs
intermittently
Cycles on overload
Check voltage. Call an electrician if not within limits.
Test capacitor. Replace if not /-10% of manufacturer's
rating.
Check bearings. Replace the motor if the blower wheel cannot
rotate freely.
Pay attention to any change from high speed to low speed.
Compressor stops
instantly after startup
Refrigerant
The amount of the refrigerant is too much, making the
compressor load too big. Recycle and recharge the refrigerant
after checking for the reason.
Compressor
The compressor is blocked inside. Replace after checking for the
reason.
Fan motor will not run
No power
Check voltage at electrical outlet. Correct if none.
Water alarm
Check and correct if water alarm happens.
Power supply cord
Check voltage at the power cord terminal on Main PCB. Replace
the power cord if none.
Transformer (discharge
transformer before testing)
Check resistance between the two input/output lines on
transformer. Replace the transformer if either the input/output is
open or the transformer is damaged.
Wire disconnected or
connection loose
Connect wire. Refer to wiring diagram for terminal identification.
Repair or replace loose terminal.
Main PCB failure
Select fan speed and check the voltage on main PCB. Replace
the main PCB if no voltage is present.
Capacitor (discharge capacitor
before testing)
Test capacitor. Replace if not /-10% of manufacturer's
rating. Replace if shorted, open or damaged.
Will not rotate
Fan blower hitting scroll. Realign assembly. Check fan motor
bearings. Replace the motor if motor shaft does not rotate.
Fan motor noise
Fan blower
Replace the fan blower if cracked, out of balance or partially
missing.
Loose screws
Tighten screws accordingly.
Worn bearings
Replace the motor if knocking sounds continue when running or
loose, or if the motor hums or noise appears to be internal while
running.
Compressor will not run
while fan motor runs
Voltage
Check voltage. Call your local utility if not within limits.
Wiring
Check the wire connections. If loose, repair or replace the
terminal. If wires are off, refer to wiring diagram for identification
and replace. Check wire locations. If not per wiring diagram,
correct.
Main PCB failure
Check voltage of main PCB. Replace the main PCB if open.
Capacitor (discharge capacitor
before testing)
Check the capacitor. Replace if not /-10% of
manufacturer’s rating. Replace if shorted, open or damaged.
Summary of Contents for SRCOOL33K
Page 4: ...4 2 Unit Dimensions 78 4 in 1991 mm 42 7 in 1085 mm 23 6 in 599 mm...
Page 7: ...7 5 PCB and Wiring Diagrams 5 1 Circuit Diagram UPPER FAN MOTOR LOWER FAN MOTOR...
Page 10: ...10 5 PCB and Wiring Diagrams 5 2 1 3 Power PCBA Gerber Layout...
Page 14: ...14 5 PCB and Wiring Diagrams 5 2 3 2 Translator PCBA Gerber Layout...
Page 39: ...39 2 Dimensiones de la Unidad 1991 mm 78 4 1085 mm 42 7 599 mm 23 6...
Page 45: ...45 5 Diagramas del Cableado y PCB 5 2 1 3 Diagrama PCBA Gerber de Energ a...
Page 49: ...49 5 Diagramas del Cableado y PCB 5 2 3 2 Diagrama del Traductor PCBA Gerber...
Page 71: ...71...
Page 72: ...72 18 06 003 93 3868_RevA 1111 W 35th Street Chicago IL 60609 EE UU www tripplite com support...