2

This manual contains important instructions and warnings that should be followed
during the installation, operation and storage of all Tripp Lite UPS Systems.

UPS Location Warnings

• Install your UPS indoors, away from excess moisture or heat, dust or

direct sunlight.

• For best performance, keep the indoor temperature between 0° C and

40° C (between 32° F and 104° F).

• Leave adequate space around all sides of the UPS for proper ventilation.

UPS Connection Warnings

• If your UPS has a corded input, connect it to a properly grounded AC

power outlet. Do not modify the UPS's plug. Do not use adapters that
eliminate the UPS's connection to ground.

• If your UPS has a hardwired input, ensure that it is properly grounded.

• Do not plug your UPS into itself; this will damage the UPS and void

your warranty.

• If you are connecting your UPS to a motor-powered AC generator,

the generator must provide clean, filtered computer-grade output.

Equipment Connection Warnings

• Do not use Tripp Lite UPS Systems for life support applications in

which a malfunction or failure of a Tripp Lite UPS System could cause
failure or significantly alter the performance of a life-support device.

• Do not connect surge suppressors to the output of your UPS. This

may damage your UPS and will void both the surge suppressor and
UPS warranties.

Battery Warnings

• Your UPS does not require routine maintenance. Do not open your

UPS for any reason. There are no user-serviceable parts inside.

• Battery replacement must be performed by qualified service personnel.

Because the batteries present a risk of electrical shock and burn from
high short-circuit current, qualified service personnel should observe
proper precautions: Unplug and turn off the UPS before performing
battery replacement. Use tools with insulated handles and replace the
existing batteries with the same number and type of new batteries
(Sealed Lead-Acid). Do not open the batteries. Do not short or bridge
the battery terminals with any object.

• The UPS batteries are recyclable. Refer to local codes for disposal

requirements, or in the US only call 1-800-SAV-LEAD for disposal
information. Do not dispose of the batteries in a fire.

• When adding external batteries, connect only Tripp Lite battery packs

of the correct voltage and type. Your UPS's External Battery Connector
should match the color of the connector of any battery pack you want
to connect.

Safety

9905251 230V SmartPro Datacenter OM.p65

8/8/00, 2:02 PM

2

Summary of Contents for SmartPro Datacenter INT

Page 1: ...f Tripp Lite Quick Installation p 3 4 Basic Operation p 5 7 Storage Service p 8 Specifications p 8 Safety p 2 1111W 35thStreet Chicago IL 60609 USA CustomerSupport 773 869 1234 www tripplite com Owner sManual SmartPro Datacenter INT Intelligent Line Interactive UPS Systems 230V Output ...

Page 2: ...lure or significantly alter the performance of a life support device Do not connect surge suppressors to the output of your UPS This may damage your UPS and will void both the surge suppressor and UPS warranties Battery Warnings Your UPS does not require routine maintenance Do not open your UPS for any reason There are no user serviceable parts inside Battery replacement must be performed by quali...

Page 3: ...ur equipment into the Power Module Turn your UPS ON Set the System Switch on the UPS s back panel to the ENABLE RIGHT position Figure1a This switch activates the battery charger and microprocessor The light will flash until you engage the ON Standby Switch to activate the ON mode EngagethemomentaryON StandbySwitchontheUPS s front panel and release it to activate the ON mode and supply power to the...

Page 4: ...which port Note the last switch on the right has no function 3 2 1 Computer communications are optional Your UPS will function properly without these connections The LAN 4 1 or Smart DB9 port is always enabled and is not controlled by the LAN Interface DIP Switches If you do not connect a computer to any of the LAN 2 1 DB9 ports set their corresponding LAN Interface DIP Switches to the DEACTIVATE ...

Page 5: ...ous beep that cannot be silenced will alert you to immediately shut down connected equipment Test your UPS s battery charge Leave your connected equipment ON With your UPS plugged in and completely turned ON engage this switch hold it there for 5 seconds and release it You will hear a series of short beeps as the UPS momentarily switches to battery to test its charge The light will turn ON and the...

Page 6: ...ged If it lights let the UPS charge for 12 hours then perform a self test If the light continues to stay on contact Tripp Lite for service This multi colored light displays 4 separate UPS load conditions It will turn from green low to yellow medium to red high as you connect equipment to show you the load level your UPS is supporting When the light is red your UPS is supporting a load above 85 of ...

Page 7: ...ipment during power failures This port uses RS 232 communications to transmit UPS and power conditions Pin 7 Transmit Pin 8 Common Pin 9 Receive Contact Tripp Lite Customer Support for more information and a list of available SNMP network management and connectivity products Contact Closure Ports Lower Rear Panel These ports labeled LAN 2 2 on the Control Module are also used to connect your UPS t...

Page 8: ...s within the 2 year warranty period enclose a copy of your sales receipt Specifications SMARTDC3000INT SMARTDC3000XRINT Output Capacity VA Watts 3000 2400 3000 2400 Battery Runtime with Battery Pack with 1 BP36V33 with 1 BP36VXR for Half Load Full Load in Minutes 26 11 84 36 Battery Recharge Time 2 4 hrs 2 4 hrs Approvals SMARTDC5000INT SMARTDC5000XLINT Output Capacity VA Watts 5000 3750 5000 3750...

Reviews: