Connecting a PAM-3 to the Output of a Unison  SU6K
or SU10K

WARNING: Before connection, make sure that your Unison system is OFF, that both input
and output breakers are switched OFF and that the system is not connected to AC power. 

(See Unison Owner's Manual.)

• Remove the PAM-3's input plug by loosening its strain relief, unscrewing and removing

the plug's housing, detaching the power cord's four internal colored wires from their
terminals and sliding off the plug. 

• Strip an additional 1" to 2" of the outer (black) casing of the power cord away from the

internal colored wires. Neatly shape the exposed metal ends of the four colored wires 
to eliminate loose strands.

• Slip the strain relief provided over the exposed end of the power cord, then thread the

exposed end of the power cord through the knockout nearest the right of the Unison's
terminal block.

• Connect the colored wires to the Unison's terminal block as shown below. The black

cord can be connected for either 240V output or 208V output. Note: the desired output
voltage MUST match the Unison's input voltage. (See Unison Owner's Manual.)

• Tighten the strain relief and affix it to the knockout.

(Note: This diagram shows the terminal block of a SU6kVA model. SU10kVA models have double connectors, but the wires are
attached to the same terminals on both models.)

®

Black
208 V

Black
240 V

Green

White

Red

93-1844 (200006177) 7/00