Emergency lighting units

EM converterLED

1. Standards

•  EN 61347-1
•  EN 61347-2-13
•  EN 61347-2-7
•  EN 55015
•  EN 61000-3-2
•  EN 61000-3-3
•  EN 61547
•  EN 60068-2-64
•  EN 60068-2-29
•  EN 60068-2-30
•  EN 62384
•  according to EN 50172
•  according to EN 60598-2-22

1.1 Glow-wire test

according to EN 61347-1 with increased temperature of 850 °C passed.

1.2 Insulation and electric strength testing of luminaires

Electronic LED-drivers can be damaged by high voltage. This has to be consid-
ered during the routine testing of the luminaires in production.

According to IEC 60598-1 Annex Q (informative only!) or ENEC 303-Annex A, 
each luminaire should be submitted to an insulation test with 500 V

DC

 for 1 sec-

ond. This test voltage should be connected between the interconnected phase 
and neutral terminals and the earth terminal. The insulation resistance must be 
at least 2 MΩ.

As an alternative, IEC 60598-1 Annex Q describes a test of the electrical 
strength with 1,500 V

AC

 (or 1,414 x 1,500 V

DC

). To avoid damage to the electronic 

devices this test 

must not be conducted

.

2. Thermal details and lifetime

2.1 Lifetime

Average lifetime 50,000 hours under rated conditions with a failure rate of 
less than 10 %. Average failure rate of 0.2 % per 1000 operating hours.

Expected lifetime with NiMH batteries
EM converterLED BASIC 202A 
MH/LiFePO4 250V

tc

65°C

70°C

75°C

lifetime

> 100,000 h > 100,000 h 94,000 h

EM converterLED BASIC 203 
MH/LiFePO4 250V

tc

65 °C

70 °C

75 °C

lifetime

> 100,000 h > 100,000 h 87,000 h

EM converterLED BASIC 204 
MH/LiFePO4 250V

tc

65 °C

70 °C

75 °C

lifetime

> 100,000 h > 100,000 h 84,000 h

EM converterLED BASIC 205 
MH/LiFePO4 250V

tc

65 °C

70 °C

75 °C

lifetime

> 100,000 h > 100,000 h 80,000 h

Expected lifetime with LiFePO

4

 batteries

EM converterLED BASIC 202A 
MH/LiFePO4 250V

tc

65°C

70°C

75°C

lifetime

> 100,000 h > 100,000 h 97,000 h

EM converterLED BASIC 203 
MH/LiFePO4 250V

tc

65 °C

70 °C

75 °C

lifetime

> 100,000 h > 100,000 h 82,000 h

EM converterLED BASIC 204 
MH/LiFePO4 250V

tc

65 °C

70 °C

75 °C

lifetime

> 100,000 h > 100,000 h 82,000 h

EM converterLED BASIC 205 
MH/LiFePO4 250V

tc

65 °C

70 °C

75 °C

lifetime

> 100,000 h > 100,000 h 81,000 h

3. Installation / Wiring

3.1 Wiring diagram

One or more LED modules with a total forward voltage of 50 to 250 V can be 
connected to the EM converterLED 250V module. These LED module(s), marked 
with “Emergency” are operated in emergency mode from the associated battery. 
In normal mains mode all LED modules are operated by the LED driver from the 
mains supply.

Use of the test switch: 
For checking the device function press the test switch for a minimum of 3 
seconds.

Meaning of marking 
Double or reinforced insulation for built-in electronic LED drivers. The control 
gear relies upon the luminaire enclosure for protection against accidental contact 
with live parts.

The emergency lighting LED driver is designed for a lifetime stated above under 
reference conditions and with a failure probability of less than 10 %.

The relation of tc to ta temperature depends also on the luminaire design. 
If the measured tc temperature is approx. 5 K below tc max., ta tempera-
ture should be checked and eventually critical components (e.g. ELCAP) 
measured. Detailed information on request.

Summary of Contents for 89800581

Page 1: ...e technology 2 pole LED module changeover and delayed power switching for the LED driver Automatic shutdown of output if LED load is out of range Constant power output Maximum light output for all LED modules Electronic charge system Deep discharge protection Short circuit proof battery connection Polarity reversal protection for battery provided by 3 pole connector Automatic detection of the conn...

Page 2: ...ery charging time for 2 h emergency lighting function according to AS 2293 3 In case of NiMH batteries Intermittent charge is used Value 1 is for 4 min charge on Value 2 is for 16 min charge off In case of LiFePO4 batteries voltage dependent constant current charging is used 4 12 h battery charging time for 2 h emergency lighting function when used with LiFePO4 batteries EL Technical data Rated su...

Page 3: ...ble jacket diameter 2 2 9 mm Ordering data Type Article number Packaging carton Packaging pallet Weight per pc EMcLED SR 28003813 10 pc s 1 260 pc s 0 08 kg Product description Optional strain relief set for independent applications Transforms the LED driver into a fully class II compatible LED driver e g ceiling installation Easy and tool free mounting to the LED driver screwless cable clamp chan...

Page 4: ...c s 0 015 kg LED EM green HO 1 0 m CON 89800271 25 pc s 200 pc s 0 015 kg LED EM green 0 6 m CON 89800472 25 pc s 200 pc s 0 009 kg LED EM green HO 0 6 m CON 89800473 25 pc s 200 pc s 0 009 kg LED EM green 0 3 m CON 89800270 25 pc s 200 pc s 0 005 kg LED EM green HO 0 3 m CON 89800272 25 pc s 200 pc s 0 005 kg Test switch EM3 ACCES SORIES Ordering data Type Article number Packaging bag Packaging c...

Page 5: ...ug connection for LED driver Connection Cable NiMH ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc CONNECTION CABLE NiMH 500mm 28002462 10 pc s 200 pc s 0 015 kg Product description Extension cable for LiFePO4 batteries Cable length 500 mm 3 pole plug connection Extension Cable LiFePO4 ACCES SORIES Ordering data Type Article number Packaging bag Packagin...

Page 6: ...5 C lifetime 100 000 h 100 000 h 87 000 h EM converterLED BASIC 204 MH LiFePO4 250V tc 65 C 70 C 75 C lifetime 100 000 h 100 000 h 84 000 h EM converterLED BASIC 205 MH LiFePO4 250V tc 65 C 70 C 75 C lifetime 100 000 h 100 000 h 80 000 h Expected lifetime with LiFePO4 batteries EM converterLED BASIC 202A MH LiFePO4 250V tc 65 C 70 C 75 C lifetime 100 000 h 100 000 h 97 000 h EM converterLED BASIC ...

Page 7: ... EM converterLED BASIC with one LED module for non maintained emergency operation P O Lout Lin N L EM converterLED BASIC Neutral Un Switched Line Test switch Indicator LED Not connected Not connected LED driver LED LED LED driver Battery Battery LED Module Emergency EM converterLED BASIC with a standard LED driver and series operation of LED modules One LED module is operated in emergency mode All...

Page 8: ...verterLED BASIC Battery Battery One LED module is operated in emergency mode All LED modules are operated in mains mode 8 9 mm wire preparation 0 5 1 5 mm 3 2 Wiring type and cross section Solid wire with a cross section of 0 5 1 5 mm Strip 8 9 mm of insulation from the cables to ensure perfect operation of terminals Wiring LED module LED driver supply 3 3 Battery connection LiFePO4 Direct connect...

Page 9: ... mm cross section and a length of 0 8 m Protect the wiring against short circuits to earth sharp edged metal parts metal cable clips louver etc to avoid the damage of the control gear To ensure that a luminaire containing LED emergency units complies with EN 55015 for radio frequency conducted interference in both normal and emergency mode it is essential to follow good practice in the wiring layo...

Page 10: ...A battery discharge current tolerance EM converterLED BASIC 202A MH LiFePO4 250V Article number 89800709 NiMH batteries 3 6 V battery voltage 780 840 mA battery discharge current tolerance LiFePO4 batteries 3 2 V battery voltage 830 950 mA battery discharge current tolerance VLED V VLED V LED current mA LED current mA EM converterLED BASIC 204 MH LiFePO4 250V Article number 89800581 NiMH batteries...

Page 11: ...of EM converterLED The max allowed output voltage U OUT of the associated LED driver applied to the EM converterLED output is 450 V voltage withstand between adjacent contact of the single switching relay of the EM converterLED The max allowed LED load of the associated LED driver is 150 W in operation The load must be an LED module Check compatibility with short function tests duration of several...

Page 12: ...fter running the test of 61347 2 7 CL 22 3 abnormal operating conditions 7 2 Battery charge discharge data EM converterLED BASIC 1 3 h Type EM converterLED BASIC 202A MH LiFePO4 250V EM converterLED BASIC 203 MH LiFePO4 250V EM converterLED BASIC 204 MH LiFePO4 250V EM converterLED BASIC 205 MH LiFePO4 250V Article no 89800709 89800592 89800581 89800582 Duration 1 h 3 h 1 h 3 h 1 h 3 h 1 h 3 h Tec...

Page 13: ...ccu NiMH Capacity 4 0 Ah International designation HRMU 19 90 Battery voltage cell 1 2 V Cell type LA Case temperature range to ensure 4 years design life 5 C to 50 C Max short term battery case temperature shorter than 1 month over the battery lifetime 70 C Max number discharge cycles 4 cycles per year plus 30 cycles during comissioning Max storage time 12 months at 5 C to 25 C 7 4 Accu LiFePO4 C...

Page 14: ...r informations refer to corresponding battery datasheet 7 7 Safety 7 7 1 Deep discharge protection When the battery remains connected without charging for a long period of time after the battery cut off of the driver the battery voltage can still drop To make sure the cells are not damaged by this voltage drop the battery protection prevents the battery from further discharge below 2 0 V 7 7 2 Ove...

Reviews: