www.tridonic.com
13
Subject to change without notice. Information provided without guarantee.
Data sheet 09/22-EM080-23
Emergency lighting units
EM converterLED
EM converterLED BASIC, 1 / 3 h, LiFePO
4
Type
EM converterLED BASIC 202A MH/
LiFePO4 250V
EM converterLED BASIC 203 MH/
LiFePO4 250V
EM converterLED BASIC 204 MH/
LiFePO4 250V
EM converterLED BASIC 205 MH/
LiFePO4 250V
Article no.
89800709
89800592
89800581
89800582
Duration
1 h
3 h
1 h
3 h
1 h
3 h
1 h
3 h
Battery charge
time
Initial charge
24 h
Fast recharge
24 h
Trickle charge
continuously and battery voltage controlled
Charging current
Initial charge
115 – 155 mA
250 – 290 mA
250 – 290 mA
430 – 470 mA
250 – 290 mA
430 – 470 mA
250 – 290 mA
430 – 470 mA
Fast recharge
115 – 155 mA
250 – 290 mA
250 – 290 mA
430 – 470 mA
250 – 290 mA
430 – 470 mA
250 – 290 mA
430 – 470 mA
Trickle charge
1
115 – 155 mA /
0 mA
250 – 290 mA /
0 mA
250 – 290 mA /
0 mA
430 – 470 mA /
0 mA
250 – 290 mA /
0 mA
430 – 470 mA /
0 mA
250 – 290 mA /
0 mA
430 – 470 mA /
0 mA
Discharge current
830 – 950 mA
830 – 950 mA
955 – 1,025 mA
955 – 1,025 mA
1,350 – 1,430 mA
1,350 – 1,430 mA
1,770 – 1,900 mA
1,770 – 1,900 mA
Charge voltage range
2
2.0 – 3.65 V
Discharge voltage range
3.65 – 2.60 V
1
Automatic recharge when battery voltage falls below 3.4 V. Charger off (0 mA) when battery voltage exceeds 3.6 V.
Note: Battery protected against operation at excessive temperatures (charging stopped when battery cell temperature < -5 °C or > 60 °C).
The emergency lighting LED driver will recharge the battery normally after running the test of 61347-2-7 CL 22.3 (abnormal operating conditions).
2
The battery will not be charged below 2.0 V.
7.3 Accu-NiMH
Capacity 4.0 Ah
International designation
HRMU 19/90
Battery voltage/cell
1.2 V
Cell type
LA
Case temperature range
to ensure 4 years design life
+5 °C to +50 °C
Max. short term battery case temperature
(shorter than 1 month over the battery lifetime) 70 °C
Max. number discharge cycles
4 cycles per year plus
30 cycles during
comissioning
Max. storage time
12 months
at +5 °C to +25 °C
7.4 Accu-LiFePO4
Capacity 1.5 Ah
International designation
lFpR 19/66
Battery voltage/cell
3.2 V
Cell type
18650
Case temperature range to ensure
4 years design life
+5 °C to +55 °C
6 years design life
+5 °C to +45 °C
8 years design life
+5 °C to +35 °C
Max. short term battery case temperature
(shorter than 1 month over the battery lifetime) 70 °C
Max. number discharge cycles
50 cycles total
Max. storage time
12 months
at +5 °C to +25 °C
7.5 Accupack-NiMH
Capacity 4.0 Ah
Battery voltage/cell
1.2 V
Cell type
LAL
Ambient temperature range
to ensure 4 years design life
+5 °C to +35 °C
tc point
+40 °C
Max. short term battery case temperature
(shorter than 1 month over the battery lifetime) 70 °C
Max. number discharge cycles
4 cycles per year plus
4 cycles during
comissioning
Max. storage time
12 months
7.6 Accupack-LiFePO4
Capacity 1.5 Ah
International designation
lFpR 19/66
Battery voltage/cell
3.2 V
Cell type
18650
Case temperature range to ensure
4 years design life
+5 °C to +45 °C
6 years design life
+5 °C to +35 °C
8 years design life
+5 °C to +25 °C
Max. short term battery case temperature
(shorter than 1 month over the battery lifetime) 70 °C
Max. number discharge cycles
50 cycles total
Max. storage time
12 months
at +5 °C to +25 °C
Only use Tridonic batteries.
Comply with UN 38.3 and IEC 62133 (safety testing) protected against over
charge, over discharge, charging at excessive temperatures, short-circuit and
over current.