Spectrum Essential Oil Storage System
TRICO CORPORATION
1235 Hickory Street; Pewaukee, WI 53072
For Customer Support: 800-558-7008
P a g e
13 | 20
WARNING:
Do not overfill the Tank. Confirm there is enough room in tank before re-
filling with a drum. Best practice is to empty the tank before re-filling.
3.
Once the tank has been emptied or confirmed to fit a drum or whatever size lubricant refill, it is
now safe to fill the tank. Place the drum, or similar container, of the lubricant to be filled next to
the Pump Stack or suction wand of the system.
4.
Attach the appropriate static discharge cabling per National Fire Protection Code 77 to prevent
static discharge from filling. Ground and bond wires must have less than one-ohm resistance for
safe usage. Check continuity before starting (NOTE: Cabling is not provided).
5.
Lift out suction wand from holder and make sure the wand is clean of any contamination. Then
insert suction wand into the full drum of lubricant to be transferred.
6.
On the Tank Manifold, close the valves to the tanks (upper valves), and open the drain valve
(lower valve) to flush the manifold of any other product. This flushing is to prevent cross-
contamination of different lubricants into the storage tank.
7.
Start the self-priming gear pump by flipping the On/Off Switch to the “ON” position. The
lubricant is now pumped from the drum, through the manifold, and out the drain hose. Once
the lubricant is seen in the drain hose, and no other products contaminating the new lubricant,
close the drain valve.
8.
Once the drain valve is closed, open the correct corresponding tank valve where the lubricant
will be stored. Now the lubricant should be transferred from the drum to the tank through the
Tank Manifold.
CAUTION:
Never leave pump unattended while using the system and the pump is
powered ON.
Suction Wand
Cross-Contamination
Drain Valve
Tank Manifold
Tank Fill Valves