background image

Outdoor Sensor - PSSENS01

3

Summer / Winter Switch

If required the CH (Central Heating) system can be
turned off at the appliance, similar to manual sum-
mer  /  winter  switch  by  press/hold  the  “+”  button
while in 

the “

StbY

” mode, the display will show

cOFF

”. Press/hold the “+” button to turn the CH

system back on, the display will show “c” followed
by CH set point temperature (Parameter 4) or CH
target temperature.

Adjusting Outdoor Reset Curve

Parameters 4, 10, 11, & 12 define the settings of the
outdoor reset curve. See Graph 1  and Table 1, page
5  for  an  example  of  modifying  the  outdoor  reset
curve.

CH Maximum Operating Setpoint
(Parameter 4)

If an outdoor temperature sensor is not connected to
the  appliance,  the  appliance  setpoint  for  a  heating
call  will  be  set  to  the  CH  Maximum  Operating
Setpoint.  If an outdoor temperature sensor is con-
nected,  the  CH  Maximum  Operating  Setpoint
becomes  the  appliance  setpoint  on  the  CH  Reset
Curve Coldest Day.  The outdoor temperature can
be monitored on the appliance display via item 4 of
the INFO menu.

CH Minimum  Operating Setpoint
(Parameter 10)

This parameter is not applicable if an outdoor sen-
sor is not connected to the appliance.  When an out-
door  temperature  sensor  is  connected,  the  CH
Minimum  Operating  Setpoint  becomes  the  appli-
ance setpoint on the CH Reset Curve Warmest Day.

CH Reset Curve Coldest Day
(Parameter 11)

This parameter is not applicable if an outdoor sen-
sor is not connected to the appliance.  When an out-
door temperature sensor is connected, the CH Reset
Curve  Coldest  Day  is  the  coldest  design  tempera-
ture of the heating system.

CH Reset Curve Warmest Day
(Parameter 12)

This parameter is not applicable if an outdoor sen-
sor is not connected to the appliance.  When an out-
door temperature sensor is connected, the CH Reset
Curve Warmest Day is the warmest design temper-
ature of the heating system.

Summary of Contents for PSSENS01

Page 1: ... screws 7 Using a 3 16 drill bit drill 2 pilot holes on the marked locations 8 Tap the enclosed plastic anchors into the pilot holes Use care not to damage the anchors 9 Mount the sensor enclosure using the screws provided Wiring the Sensor 1 Remove the sealing nut and sealing gasket from the sensor enclosure 2 Route 18 AWG 2 wire cable or similar wire cable through the sealing nut and gasket Conn...

Page 2: ...Outdoor Sensor PSSENS01 2 The following section applies to PRESTIGE using the Honeywell Type 5 MCBA Control This Control is identified as Honeywell MCBA 54201 NOTICE ...

Page 3: ...nected the CH Maximum Operating Setpoint becomes the appliance setpoint on the CH Reset Curve Coldest Day The outdoor temperature can be monitored on the appliance display via item 4 of the INFO menu CH Minimum Operating Setpoint Parameter 10 This parameter is not applicable if an outdoor sen sor is not connected to the appliance When an out door temperature sensor is connected the CH Minimum Oper...

Page 4: ...owing sequence Press STEP once 1140 Press STEP x2 2_01 Press STEP x3 3_01 Press STEP x4 4186 Press STEP x5 P_10 Press STEP x6 P_11 Etc After Parameter 4 the display will show P followed by the parameter number Once a particular para meter is reached the display will change to show the current setting of that parameter The actual parameter values displayed on the display may vary depending on the a...

Page 5: ... Parameter 4 Set Point Parameter 10 Set PointParameter 12 Setting Parameter 11 Setting Table 1 Outdoor Air Temperature Reset Example Graph 1 Outdoor Air Temperature Reset Curve Example Graph 1 illustrates Parameter 4 adjusted to 140ºF target temperature at 0ºF outdoor air temperature Note Factory setting of Parameter 4 is 186ºF ...

Page 6: ...Outdoor Sensor PSSENS01 6 The following section applies to the CHALLENGER condensing boiler and It s internal control module NOTICE ...

Page 7: ...the coldest design tempera ture of the heating system CH Reset Curve Warmest Day Parameter 7 This parameter is not applicable if an outdoor sen sor is not connected to the appliance When an out door temperature sensor is connected the CH Reset Curve Warmest Day is the warmest design temper ature of the heating system Changing Outdoor Reset Parameters 1 Press the service button until the appropriat...

Page 8: ... Parameter 5 Set Point Parameter 7 Setting Parameter 6 Setting Graph 2 Outdoor Air Temperature Reset Curve Example Table 2 Outdoor Air Temperature Reset Example Graph 2 illustrates CH Setpoint adjusted to 140ºF target temperature at 0ºF outdoor air temperature Note Factory setting of CH set point is 186ºF Outdoor CH target Temp 10ºF or Lower 140ºF 30ºF 117ºF 50ºF 93ºF 64ºF or Higher 77ºF ...

Reviews: