Outdoor Sensor - PSSENS01
Entering MCBA Access Code
The installer must enter the MCBA Access Code to
adjust the advanced parameter settings of the
MCBA. The Access Code can be entered as follows:
1. Press the MODE button until the display shows
STbY
.
2. Press and hold the MODE and STEP buttons
together for 2 to 3 seconds until the display
shows
CODE
.
3. Press the STEP button once and the display will
show
C_
XX
where
XX
represents a random
number.
4. Press the “+” or “–“ buttons to change the num-
ber displayed to read
C_54
.
. Press and hold the
“+” or “–“ button to rapidly change the number.
5. When the display reads
C_54
, press the STORE
button to save the Access Code. The display
should flash to indicate that the Access Code
was saved.
After the Access Code has been entered, the
advanced parameters can be accessed by pressing
the MODE button until the display shows
PARA
.
Once the display shows
PARA
, press the STEP but-
ton to reach the appropriate parameter. The display
should follow the following sequence:
Press STEP once-
1140
Press STEP x2 -
2_01
Press STEP x3 -
3_01
Press STEP x4 -
4186
Press STEP x5 -
P_10
Press STEP x6 -
P_11
Etc......
After Parameter 4, the display will show P followed
by the parameter number. Once a particular para-
meter is reached, the display will change to show
the current setting of that parameter.
The actual parameter values displayed on the
display may vary depending on the application,
but the sequence will always occur in the order
shown.
Changing a Parameter Setting
1. Use the “+” or “–“ button to change the para-
meter setting.
2. Press the STORE button to save the change.
The display should flash to indicate that the
change was saved.
3. Press the RESET button to leave the Access
Code mode.
Parameter 4 is adjustable from 86ºF to
194ºF. The factory setting is 186ºF. Adjusting
this parameter may affect the performance
of the appliance.
•
Once Parameter 4 is displayed, use the + or -
button to modify the parameter setting.
•
Once the desired parameter setting is reached
press STORE to save the value. The display
will flash once to confirm the data has been
saved.
•
To activate the stored parameter value, press
MODE twice to return to the STBY mode.
NOTICE
NOTICE
4