Outdoor Sensor - PSSENS01

7

Adjusting Outdoor Reset Curve

The appliance CH set point along with Parameters
5,  6  &  7  define  the  settings  of  the  outdoor  reset
curve.  See  Graph  2  and  Table  2,  page  8  for  an
example of modifying the outdoor reset curve.

CH (Maximum Operating Temperature)

If an outdoor temperature sensor is not connected to
the  appliance,  the  appliance  setpoint  for  a  heating
call  will  be  set  to  the  CH  Setpoint.    If  an  outdoor
temperature sensor is connected, the CH Maximum
Appliance  Operating  Setpoint  becomes  the  appli-
ance setpoint on the CH Reset Curve Coldest Day.  

CH Minimum Boiler Operating Setpoint
(Parameter 5)

This parameter is not applicable if an outdoor sen-
sor is not connected to the appliance.  When an out-
door  temperature  sensor  is  connected,  the  CH
Minimum  Appliance  Operating  Setpoint  becomes
the  appliance  setpoint  on  the  CH  Reset  Curve
Warmest Day.

CH Reset Curve Coldest Day
(Parameter 6)

This parameter is not applicable if an outdoor sen-
sor is not connected to the appliance.  When an out-
door temperature sensor is connected, the CH Reset
Curve  Coldest  Day  is  the  coldest  design  tempera-
ture of the heating system.

CH Reset Curve Warmest Day
(Parameter 7)

This parameter is not applicable if an outdoor sen-
sor is not connected to the appliance.  When an out-
door temperature sensor is connected, the CH Reset
Curve Warmest Day is the warmest design temper-
ature of the heating system.

Changing Outdoor Reset Parameters

1. Press the

service button until the appropriate

parameter number 

or 

or 

appears in the

operating display.

2. Press the 

or

buttons to set the desired para-

meter value on the main display.

3. Once  the  desired  parameter  value  has  been

entered  press 

reset until a 

appears on the

operating display.

The appliance control module has now been repro-
grammed with the desired parameter values.

Pressing the 

ON/OFF button will exit the

parameter  setting  mode  without  stroing  the
parameter changes.

Pressing  the 

service  button  for  a  period

exceeding 5 seconds will reset the parameter
settings to the factory default. The main and
service display will show 

when this

occurs.

P

NOTICE

F - S E T

Factory Setting

Minimum 

Setting

Maximum

Setting

186ºF

86ºF

194ºF

Factory Setting

Minimum 

Setting

Maximum

Setting

64ºF

60ºF

78ºF

Factory Setting

Minimum 

Setting

Maximum

Setting

00ºF

-22ºF

50ºF

Factory Setting

Minimum 

Setting

Maximum

Setting

86ºF

60ºF

140ºF

Summary of Contents for PSSENS01

Page 1: ... screws 7 Using a 3 16 drill bit drill 2 pilot holes on the marked locations 8 Tap the enclosed plastic anchors into the pilot holes Use care not to damage the anchors 9 Mount the sensor enclosure using the screws provided Wiring the Sensor 1 Remove the sealing nut and sealing gasket from the sensor enclosure 2 Route 18 AWG 2 wire cable or similar wire cable through the sealing nut and gasket Conn...

Page 2: ...Outdoor Sensor PSSENS01 2 The following section applies to PRESTIGE using the Honeywell Type 5 MCBA Control This Control is identified as Honeywell MCBA 54201 NOTICE ...

Page 3: ...nected the CH Maximum Operating Setpoint becomes the appliance setpoint on the CH Reset Curve Coldest Day The outdoor temperature can be monitored on the appliance display via item 4 of the INFO menu CH Minimum Operating Setpoint Parameter 10 This parameter is not applicable if an outdoor sen sor is not connected to the appliance When an out door temperature sensor is connected the CH Minimum Oper...

Page 4: ...owing sequence Press STEP once 1140 Press STEP x2 2_01 Press STEP x3 3_01 Press STEP x4 4186 Press STEP x5 P_10 Press STEP x6 P_11 Etc After Parameter 4 the display will show P followed by the parameter number Once a particular para meter is reached the display will change to show the current setting of that parameter The actual parameter values displayed on the display may vary depending on the a...

Page 5: ... Parameter 4 Set Point Parameter 10 Set PointParameter 12 Setting Parameter 11 Setting Table 1 Outdoor Air Temperature Reset Example Graph 1 Outdoor Air Temperature Reset Curve Example Graph 1 illustrates Parameter 4 adjusted to 140ºF target temperature at 0ºF outdoor air temperature Note Factory setting of Parameter 4 is 186ºF ...

Page 6: ...Outdoor Sensor PSSENS01 6 The following section applies to the CHALLENGER condensing boiler and It s internal control module NOTICE ...

Page 7: ...the coldest design tempera ture of the heating system CH Reset Curve Warmest Day Parameter 7 This parameter is not applicable if an outdoor sen sor is not connected to the appliance When an out door temperature sensor is connected the CH Reset Curve Warmest Day is the warmest design temper ature of the heating system Changing Outdoor Reset Parameters 1 Press the service button until the appropriat...

Page 8: ... Parameter 5 Set Point Parameter 7 Setting Parameter 6 Setting Graph 2 Outdoor Air Temperature Reset Curve Example Table 2 Outdoor Air Temperature Reset Example Graph 2 illustrates CH Setpoint adjusted to 140ºF target temperature at 0ºF outdoor air temperature Note Factory setting of CH set point is 186ºF Outdoor CH target Temp 10ºF or Lower 140ºF 30ºF 117ºF 50ºF 93ºF 64ºF or Higher 77ºF ...

Reviews: