Outdoor Sensor - PSSENS01
7
Adjusting Outdoor Reset Curve
The appliance CH set point along with Parameters
5, 6 & 7 define the settings of the outdoor reset
curve. See Graph 2 and Table 2, page 8 for an
example of modifying the outdoor reset curve.
CH (Maximum Operating Temperature)
If an outdoor temperature sensor is not connected to
the appliance, the appliance setpoint for a heating
call will be set to the CH Setpoint. If an outdoor
temperature sensor is connected, the CH Maximum
Appliance Operating Setpoint becomes the appli-
ance setpoint on the CH Reset Curve Coldest Day.
CH Minimum Boiler Operating Setpoint
(Parameter 5)
This parameter is not applicable if an outdoor sen-
sor is not connected to the appliance. When an out-
door temperature sensor is connected, the CH
Minimum Appliance Operating Setpoint becomes
the appliance setpoint on the CH Reset Curve
Warmest Day.
CH Reset Curve Coldest Day
(Parameter 6)
This parameter is not applicable if an outdoor sen-
sor is not connected to the appliance. When an out-
door temperature sensor is connected, the CH Reset
Curve Coldest Day is the coldest design tempera-
ture of the heating system.
CH Reset Curve Warmest Day
(Parameter 7)
This parameter is not applicable if an outdoor sen-
sor is not connected to the appliance. When an out-
door temperature sensor is connected, the CH Reset
Curve Warmest Day is the warmest design temper-
ature of the heating system.
Changing Outdoor Reset Parameters
1. Press the
service button until the appropriate
parameter number
or
or
appears in the
operating display.
2. Press the
or
buttons to set the desired para-
meter value on the main display.
3. Once the desired parameter value has been
entered press
reset until a
appears on the
operating display.
The appliance control module has now been repro-
grammed with the desired parameter values.
Pressing the
ON/OFF button will exit the
parameter setting mode without stroing the
parameter changes.
Pressing the
service button for a period
exceeding 5 seconds will reset the parameter
settings to the factory default. The main and
service display will show
when this
occurs.
P
NOTICE
F - S E T
Factory Setting
Minimum
Setting
Maximum
Setting
186ºF
86ºF
194ºF
Factory Setting
Minimum
Setting
Maximum
Setting
64ºF
60ºF
78ºF
Factory Setting
Minimum
Setting
Maximum
Setting
00ºF
-22ºF
50ºF
Factory Setting
Minimum
Setting
Maximum
Setting
86ºF
60ºF
140ºF