background image

Prestige SOLO 399

Burner Mounting Plate Kit

4

Do not check for gas leaks with an open flame.

Use  a  bubble  test.    Failure  to  check  for  gas

leaks can cause severe personal injury, death

or substantial property damage.

24. Install  the  appropriate  new  igniter  and  gasket

for the unit.

25. Re-attach  the  ignition  cable  (MCBA)  and  the

ground wire to the ignitor.

26. Reattach the air inlet elbow to the venturi.
27. Reposition the control panel.
28. Replace the front jacket panel and secure with

the thumb screw on the upper edge of the unit.

29. Install the top jacket access panel

30. Turn power to the unit “ON”.  The unit is now

ready to be placed back into service.

COMBUSTION TEST/ADJUSTMENT 

The installer must perform a complete combustion

check to ensure the following combustion levels are

met at high and low input firing rates  and the burn-

er is operating at optimum conditions.

The  combustion  testing  and  adjustments

must  be  performed  by  a  qualified  installer,

service agency or the gas supplier. All com-

bustion measurements must be perform with

calibrated equipment to ensure proper read-

ings and accuracy.

Failure  to  perform  a  complete  combustion

test  at  both  high  and  low  input  rates  may

result in incomplete combustion and the pro-

duction  of  carbon  monoxide,  which  can

cause  severe  personal  injury,  death  or  sub-

stantial property damage.

MCBA Instructions

1. Manually place the boiler into high fire mode

by pressing the MODE button with  “+”  button

simultaneously  on  the  control  panel  display

while in the standby (STBY) mode.

WARNING

WARNING

WARNING

Natural Gas

Propane

O2 Min.

2.30%

3.70%

O2 Max.

5.30%

5.20%

CO2 Min.

8.80%

10.00%

CO2 Max.

10.50%

11.00%

CO Max.

100 ppm

100 ppm

Table 1: Recommended Combustion Levels

2

3

5

4

1

1. Brown (MCBA)/ Black (Trimax) Wire

2. Blue (MCBA)/ White (Trimax) Wire

3. Throttle Screw

4. Offset Pressure Cover Screw

5. Inlet Pressure Tap

Fig. 5: PRESTIGE Solo 399 Gas Valve

Summary of Contents for PSRKIT39

Page 1: ...rdous situation which if ignored can result in serious injury or substantial property damage For your safety turn off electrical power supply at service panel and allow unit to cool before proceeding...

Page 2: ...ors from the blower and remove the blower retaining nuts Remove the blower with venturi and gas valve from the unit 11 Remove the 10 mm nuts and remove the burn er mounting plate assembly from the hea...

Page 3: ...g nuts are in place use a wrench to tighten using an alternating pattern until the gasket is slightly compressed See Table 2 page 7 for torque specifications 21 Re assemble the blower onto the burner...

Page 4: ...is operating at optimum conditions The combustion testing and adjustments must be performed by a qualified installer service agency or the gas supplier All com bustion measurements must be perform wit...

Page 5: ...wrench see Fig 5 as follows Counter clockwise adjustment of OFFSET SCREW at Low Fire O2 increases and CO2 decreases Clockwise adjustment of OFFSET SCREW at Low Fire O2 decreases and CO2 increases 5 P...

Page 6: ...mbustion level is set at high fire manually place the boiler into low fire mode by pressing the LEFT button to adjust firing rate down to 1 low fire 8 If the CO2 combustion level at low fire is not wi...

Page 7: ...for latest recommendations 2 Wear long sleeved loose fitting clothing gloves and eyes protection 3 Assure adequate ventilation 4 Wash with soap and water after contact 5 Wash potentially contaminated...

Reviews: