Prestige SOLO 399
Burner Mounting Plate Kit
4
Do not check for gas leaks with an open flame.
Use a bubble test. Failure to check for gas
leaks can cause severe personal injury, death
or substantial property damage.
24. Install the appropriate new igniter and gasket
for the unit.
25. Re-attach the ignition cable (MCBA) and the
ground wire to the ignitor.
26. Reattach the air inlet elbow to the venturi.
27. Reposition the control panel.
28. Replace the front jacket panel and secure with
the thumb screw on the upper edge of the unit.
29. Install the top jacket access panel
30. Turn power to the unit “ON”. The unit is now
ready to be placed back into service.
COMBUSTION TEST/ADJUSTMENT
The installer must perform a complete combustion
check to ensure the following combustion levels are
met at high and low input firing rates and the burn-
er is operating at optimum conditions.
The combustion testing and adjustments
must be performed by a qualified installer,
service agency or the gas supplier. All com-
bustion measurements must be perform with
calibrated equipment to ensure proper read-
ings and accuracy.
Failure to perform a complete combustion
test at both high and low input rates may
result in incomplete combustion and the pro-
duction of carbon monoxide, which can
cause severe personal injury, death or sub-
stantial property damage.
MCBA Instructions
1. Manually place the boiler into high fire mode
by pressing the MODE button with “+” button
simultaneously on the control panel display
while in the standby (STBY) mode.
WARNING
WARNING
WARNING
Natural Gas
Propane
O2 Min.
2.30%
3.70%
O2 Max.
5.30%
5.20%
CO2 Min.
8.80%
10.00%
CO2 Max.
10.50%
11.00%
CO Max.
100 ppm
100 ppm
Table 1: Recommended Combustion Levels
2
3
5
4
1
1. Brown (MCBA)/ Black (Trimax) Wire
2. Blue (MCBA)/ White (Trimax) Wire
3. Throttle Screw
4. Offset Pressure Cover Screw
5. Inlet Pressure Tap
Fig. 5: PRESTIGE Solo 399 Gas Valve