TriangleTube PRESTIGE Excellence PSRKIT01 Manual Download Page 8

PRESTIGE Excellence

HX Field Replacement

Kit 

8

8. Install  cabinet  gasket  where  heat  exchanger

condensate drain nipple penetrates the cabinet.

9. Install the condensate drain assembly as shown

in Fig. 10.

10. A  new  metal  washer  must  be  installed  when

installing the condensate drain assembly onto a

polypropylene condensate pan. The new metal

washer must first be cut using a pair of diagonal

cutting  pliers  to  make  it  into  a  split  washer.

Insert the split metal washer into the retaining

nut and screw onto the condensate drain assem-

bly without rubber gaskets. Use the condensate

drain assembly as a tool to press the retaining

nut with split metal washer onto the polypropy-

lene  condensate  pan.  Unscrew  the  condensate

drain assembly and proceed to the next step.

Ensure the installation of the condensate drain

assembly  included  the  metal  washer  when

attaching  to  a  polypropylene  condensate  pan.

Failure to comply could result in the trap assem-

bly dislocating from the boiler.

11. Slide the retaining nut, and rubber seals from the

condensate drain assembly over the heat exchang-

er condensate drain nipple. Connect the condensate

drain assembly to the retaining nut and tighten. 

Ensure the condensate drain assembly contains

the plastic seated ball. Do not install the conden-

sate drain assembly if the ball is lost or missing,

replace the entire assembly.

Installation of Gas Connection

1. Install  the  gas  piping  inside  the  unit  if  it  was

removed for additional clearance/access.

2. Connect gas piping to the gas valve at the brass

union located just below the gas valve. Tighten

the union using two wrenches. See Table 2, page

14 for torque specifications.

Installation of Stainless Steel Vent Outlet

Adapter

1. Ensure flue gasket is seated properly in the heat

exchanger adapter.  Apply clean water to the bot-

tom of the vent outlet adapter and flue gasket.

(Fig. 11).  

2. Insert vent outlet adapter  through the top jacket

panel  into the heat exchanger adapter. (Fig. 11).

Use  a  slight  twist  motion  with  a  downward

force as it is inserted into the adapter.  Ensure

the gasket remains seated in the heat exchanger

adapter.

WARNING

WARNING

Flexible Tubing

(or 3/4 PVC/ 

CPVC Piping

to Drain)

Compression

Nut with 

Rubber Seal

Fill Plug

with Vaccum

Break Port

Condensate

Drain Assembly

Plastic Ball

(Not shown)

Retaining Nut

Place the Metal 

Washer and (2) 

Rubber Gaskets 

in this Order for  

Proper Seal.

Fig.10: Condensate Drain Assembly

Summary of Contents for PRESTIGE Excellence PSRKIT01

Page 1: ...1 PSRKIT01 Heat Exchanger Assembly X 1 PTRKIT124 Heat Exchanger Assembly X 1 PSRKIT76 Heat Exchanger Assembly X 1 PTRKIT125 Heat Exchanger Assembly X Indicates a potentially hazardous situation which...

Page 2: ...Attach a hose to external boiler drain Place other end of this hose to a suitable drain 8 Open external boiler drain valve and begin draining the boiler To assist in the draining of the boiler remove...

Page 3: ...d from the boiler it should be inspected for deformation damage or corrosion If there are any signs of deformation damage or corrosion on the vent outlet adapter replace it immediately Check condition...

Page 4: ...ated at the top of the heat exchanger 10 Disconnect the blue wire leads from return tem perature sensor Shown as item 4 in Fig 1 located at the bottom of the heat exchanger 11 Disconnect the orange wi...

Page 5: ...hillips Torx head screw driver provided in the kit and remove the blower gas valve venturi Gas valve and ven turi assembly can remain connected to the blower housing Discard old blower gasket Fig 5 Re...

Page 6: ...avoid vertical motion of the heat exchanger during transport and is not required to be installed with the replacement heat exchanger 2 Lift the heat exchanger about 4 to 6 to disen gage from the rear...

Page 7: ...ly connection of the new heat exchanger Use a new boiler piping gasket provided in the kit between heat exchanger and supply pipe Tighten the brass union nut ensuring a leak tight seal Use care when t...

Page 8: ...le Connect the condensate drain assembly to the retaining nut and tighten Ensure the condensate drain assembly contains the plastic seated ball Do not install the conden sate drain assembly if the bal...

Page 9: ...and the gasket is reseated in the adapter Failure to comply could result in leakage of flue prod ucts into the surrounding area resulting in death or personal injury Installation of Polypropylene Vent...

Page 10: ...erature sensor wires of the boiler wiring harness using the included Wire Taps Follow the Harness Adapter instructions above then plug the Harness Adapter into the supply tem perature sensor 4 Reconne...

Page 11: ...8 Connect ignition cable to the TriMax control module and install rear control box cover 9 Install the air intake pipe back on the venturi air inlet connection Make sure the ignition cable is secured...

Page 12: ...ents must be performed with calibrated equip ment to ensure proper readings and accuracy Failure to perform a complete combustion test at both high and low input rates may result in incom plete combus...

Page 13: ...enter the access code 3 Press the RIGHT button to highlight the Manual Operation icon then press the OK button 4 Press the OK button while the FAN icon is highlighted to manually fire the burner and...

Page 14: ...the plastic OFFSET SCREW see Fig 14 using a T 40 Torx wrench as follows Counter clockwise adjustment of OFFSET SCREW at Low Fire 1 firing rate O2 increases and CO2 decreases Clockwise adjustment of OF...

Reviews: