21
Error Codes
Error
Code
Error Code Description
Possible Remedies
Lockout
Type
65
Supply Water Valve Error
Press the Power button to clear the Error Code.
If Error happens again:
1. Turn power OFF and ON at the main power switch internal to the water heater.
2. Check wiring connections to supply water valve. Ensure all are secure.
3. Replace supply water valve.
4. If the problem persists, replace the main control.
Hard Lock
66
Mixing Valve Error
Press the Power button to clear the Error Code.
If Error happens again:
1. Turn power OFF and ON at the main power switch internal to the water heater.
2. Check wiring connections to mixing valve. Ensure all are secure.
3. Replace mixing valve.
4. If the problem persists, replace the main control.
Hard Lock
67
AGM Error
Press the Power button to clear the Error Code.
If Error happens again:
1. Turn power OFF and ON at the main power switch internal to the water heater.
2. Ensure fan inlet hole is completely open after turning the power OFF and ON.
3. Check wiring connections to the AGM. Ensure all are secure.
4. Check AGM operation.
5. Replace AGM.
6. If the problem persists, replace the main control.
Hard Lock
72
Flame Signal Detected before Igni-
tion
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check the water heater cover. Ensure it is secure. Flame detection sensor can de-
tect an external light source.
2. Check flame detection sensor. Ensure connections are secure. Normal operating
settings are more than 2.5DC before ignition, less than 2.5DC after ignition.
3. If the problem persists, replace the main control.
Soft Lock
73
DIP Switch is abnormal
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check dip switches. Ensure switches match the ratings plate requirements of the
water heater.
2. If the problem persists, replace the main control.
Soft Lock
76
Poor Communication
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check connections from main control to display panel.
2. If the problem persists, replace the display and/or the main control.
Soft Lock
94
Exhaust NTC detects Vent Tempera-
ture is Greater than 149°F (65°C)
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check if dip switch High Fire setting is ON. Switches 6 and 7 should be OFF for
normal operation.
2. Check exhaust temperature sensor. Ensure connections are secure.
3. Check sensor resistance. If resistance is zero, replace the sensor.
4. Check exhaust vent for blockage.
5. If the problem persists, replace the control.
6. If the problem persists, replace the heat exchanger.
* In Case Of PVC Vent Setting, Exhaust NTC detects Vent Temperature is Greater
than 149°F (65°C)
Hard Lock