background image

cut off leaving approximately 12

"

 inside the junction 

box. (See fig. 10).

STEP 10. Go to the fan motor and connect the wires 

as shown in appropriate wiring diagram. (See fig. 9). 
Route the wire from the motor through the junction 
box, anchor securely, and cut leaving approximately 
12

"

 in the box. (See fig. 10).

STEP 11. For the power source, it will be necessary 

to route from the fuse/circuit breaker box to the 
junction box in the attic space. To accomplish this, it 
will be necessary to add a circuit breaker. An alternate 
method is to use an existing electrical source already 
in the attic space. With either method, route this wire 
to another hole in the junction box and cut off leaving 
approximately 12

of wire in the box. YOU SHOULD 

NOW HAVE THREE SEPARATE LINES (WIRES) IN THE 
JUNCTION B0X, ONE FROM THE SWITCH LOCATION, 
ONE FROM THE FAN MOTOR AND ONE FROM THE 
POWER SOURCE.

STEP 12. Using wire nuts connect all wires as 

shown in the wiring diagram. It will be necessary to cut 
off some of the excess wire in the switch and junction 
boxes since these wires must be placed inside these 
boxes with the covers anchored securely in place. 
When the switch is installed in the switch box BE SURE 
THAT THE WALL SWITCH IS IN THE OFF POSITION. 

STEP 13. Return to the attic. MAKE CERTAIN THAT 

THE FAN BLADES ARE CLEAR AND THAT NO WIRES 
OR OTHER OBSTRUCTIONS ARE NEAR THE BLADES.

STEP 14. Verify all electrical connections. Switch 

power ON at the Fuse/Circuit Breaker Box. 

NOTE: WINDOWS IN AT LEAST ONE ROOM OF 

STRUCTURE MUST BE OPEN BEFORE TESTING THE 
FAN.

STEP 15.  TESTING THE FAN.  (See  fig.  9).  Turn 

the switch on to High, allow the fan to run for several 
seconds, then turn the switch to Low. 

STEM 16. With the fan operating, return to the attic 

and observe the fan. If the V-Belt is vibrating, turn 
OFF the fan, and switch the power at the Fuse/Circuit 
Box to the OFF position. See the SAFETY RULES on 
page 1. Move the fan spring to the end hole of the 
motor-mounting plate. (See page 7). After repositioning 
the spring, switch the power at the Fuse/Circuit Breaker 
Box to the On position. Re-test the fan.

STEP 17. After testing, replace the insulation around 

the plenum and new framing.

Junction Box

To 120V

Power Source

Wall Switch

Page 6

ELECTRICAL WIRING, continued

Fig. 10

Fig. 9

Summary of Contents for COMFORT COOLER CC2422

Page 1: ... 60 Hz cycle current Permanent THREE WIRE grounded wiring must be used DO NOT USE AN EXTENSION CORD To avoid risk of electrical shock fire and other injuries DISCONNECT MAIN POWER SUPPLY prior to installation This fan is to be mounted in a location where the entrance of drawn in water rain is unlikely If shutter is removed for servicing replace before normal operation WARNING To reduce the risk of...

Page 2: ...e fan using lumber plywood or other material a minimum of 3 4 thick The platform must be constructed so that it supports all four sides of the fan and should be wide enough to prevent Attic Air from being drawn Location of Fan The most logical place to locate your whole house fan is near the central part of the house Check attic area to be certain there is a clearance space above the fan equal to ...

Page 3: ...of the joints of the new framing platform and plenum with duct tape or aluminum foil tape AS SERIES SHUTTER INSTALLATION continued STEP 9 Place the fan on the plenum making sure that the rubber isolation mount is in place between the fan and plenum DO NOT REPLACE SCREWS This is to permit the fan to float on the rubber mount which helps reduce noise See fig 4 STEP 10 Install the flush mounted ceili...

Page 4: ...ling and against the joist that will be the center of the fan With a pencil trace around the template Repeat this procedure on the exact opposite side of the joist Drill a 1 4 hole at each corner of the pencil lines YOU SHOULD HAVE EIGHT 8 HOLES From directly below the attic check to be sure that the location is correct STEP 2 Return to the attic and using a utility knife or sheetrock saw carefull...

Page 5: ... wire is anchored to the box correctly and insert the box into the rectangular hole When the box is installed correctly the sides of the box should be flush with the outside surface of the sheetrock and the box must be secured to the stud NOTE SINCE THERE ARE VARIOUS TYPES OF ELECTRICAL boxes THAT CAN BE USED CONSULT YOUR LOCAL ELECTRICAL SUPPLIER FOR HIS SUGGESTIONS STEP 9 Return to the location ...

Page 6: ...n boxes since these wires must be placed inside these boxes with the covers anchored securely in place When the switch is installed in the switch box BE SURE that the wall switch IS IN THE OFF POSITION STEP 13 Return to the attic Make certain that the fan blades are clear and that no wires or other obstructions are near the blades STEP 14 Verify all electrical connections Switch power ON at the Fu...

Page 7: ... Pulley 48 10 Fan Pulley 24 Fan Pulley 30 Fan Pulley 36 Fan Pulley 42 Fan Pulley 48 11 Fan Shaft 12 Bearing 2 req d 2 Speed Wall Switch 12 Hour Timer REPAIR REPLACEMENT PARTS REPAIR PARTS When ordering repair parts always give the following information 1 Part description 2 Fan model no 3 Fan serial no 10 12 11 8 12 4 2 5 3 7 6 9 1 TO REPOSITION OR REPLACE SPRING A Remove V Belt 8 B Hook spring 6 a...

Page 8: ...tion affixing of any parts or attachments not authorized by Manufacturer or loss of parts In no event shall Manufacturer be liable for any special incidental or consequential damages which may result from any defect in material or workmanship It is expressly understood that Buyer s sole and exclusive remedy shall be repair or replacement of defective parts and that Triangle Engineering shall not b...

Reviews: