background image

Page 4

STEP 1.  After the installation site has been 

selected for the fan, remove any insulation from the 

area and select a ceiling joist to be the center line 

of the fan.

Use the shutter carton to make a template for the 

opening your shutter requires. (See above) FROM 

THE ATTIC SIDE OF THE INSTALLATION SITE place 

“CSS” SERIES SHUTTER INSTALLATION

Models CSS-24, CSS-30 & CSS-36, install on joists with 16

"

 or 24

"

 centers.

Model CSS-42 installs on 24” centers only.

CAUTION: DO NOT CUT THE SHUTTER OPENING 

THE SAME SIZE AS THE FAN OPENING. 

Use the shutter inside dimensions as shown in the 

shutter specification chart below.

OPENING SIZES

 - Installs centered on a joist with 16

"

 

or 24

"

 

centers.

Cut two openings, one on each side of center joist per shutter model:

 

 

  Model 

Fan Size 

Outside Dimension 

Opening Size

 CSS-24 

24

"

 24

"

 x 32

"

 10

1

/

4

"

 x 30

1

/

4

"

 CSS-30 

30

"

 32

"

 x 35

"

 14

1

/

4

"

 x 34

1

/

4

"

 CSS-36 

36

"

 32

"

 x 43

"

 14

1

/

4

"

 x 41

1

/

4

"

  

*

CSS-42 42

"

 

38

"

 x 49

"

 

17

1

/

4

"

 x 46

3

/

4

"

*

For 24

"

 o.c. joists only

the template on the ceiling and against the joist that 

will be the center of the fan. With a pencil trace 

around the template. Repeat this procedure on the 

exact opposite side of the joist. Drill a 

1

/

4

"

 hole at each 

corner of the pencil lines. YOU SHOULD HAVE EIGHT 

(8) HOLES. From directly below the attic, check to be 

sure that the location is correct.

STEP 2. Return to the attic, and using a utility knife 

or sheetrock saw carefully cut the shutter opening 

following the pattern on both sides of the joist. (See 

fig. 5).

DO NOT REMOVE THE SHEETROCK 

FROM THE CENTER JOIST.

STEP 3. Frame the opening using lumber EQUAL 

TO THE SIZE OF THE EXISTING JOISTS. (See fig. 6).

STEP 4. If the opening is less than the distance 

between the joists, fasten supports between the new 

framing along the edge of the opening. (See fig. 8.).

STEP 5. Remove the two (2) screws that secure the 

fan frame to the plenum. Pass the fan and plenum into 

the attic through the framed opening in the ceiling.* 

Set them aside at this time.

Platform

New framing

Fig. 5

Fig. 6

Fig. 7

“CSS” SHUTTERS

*

If the fan does not fit through 

the framed opening, use your 

attic access opening. The current 

building code requires this access 

opening to be at least 22" x 30".

Summary of Contents for COMFORT COOLER CC2422

Page 1: ... 60 Hz cycle current Permanent THREE WIRE grounded wiring must be used DO NOT USE AN EXTENSION CORD To avoid risk of electrical shock fire and other injuries DISCONNECT MAIN POWER SUPPLY prior to installation This fan is to be mounted in a location where the entrance of drawn in water rain is unlikely If shutter is removed for servicing replace before normal operation WARNING To reduce the risk of...

Page 2: ...e fan using lumber plywood or other material a minimum of 3 4 thick The platform must be constructed so that it supports all four sides of the fan and should be wide enough to prevent Attic Air from being drawn Location of Fan The most logical place to locate your whole house fan is near the central part of the house Check attic area to be certain there is a clearance space above the fan equal to ...

Page 3: ...of the joints of the new framing platform and plenum with duct tape or aluminum foil tape AS SERIES SHUTTER INSTALLATION continued STEP 9 Place the fan on the plenum making sure that the rubber isolation mount is in place between the fan and plenum DO NOT REPLACE SCREWS This is to permit the fan to float on the rubber mount which helps reduce noise See fig 4 STEP 10 Install the flush mounted ceili...

Page 4: ...ling and against the joist that will be the center of the fan With a pencil trace around the template Repeat this procedure on the exact opposite side of the joist Drill a 1 4 hole at each corner of the pencil lines YOU SHOULD HAVE EIGHT 8 HOLES From directly below the attic check to be sure that the location is correct STEP 2 Return to the attic and using a utility knife or sheetrock saw carefull...

Page 5: ... wire is anchored to the box correctly and insert the box into the rectangular hole When the box is installed correctly the sides of the box should be flush with the outside surface of the sheetrock and the box must be secured to the stud NOTE SINCE THERE ARE VARIOUS TYPES OF ELECTRICAL boxes THAT CAN BE USED CONSULT YOUR LOCAL ELECTRICAL SUPPLIER FOR HIS SUGGESTIONS STEP 9 Return to the location ...

Page 6: ...n boxes since these wires must be placed inside these boxes with the covers anchored securely in place When the switch is installed in the switch box BE SURE that the wall switch IS IN THE OFF POSITION STEP 13 Return to the attic Make certain that the fan blades are clear and that no wires or other obstructions are near the blades STEP 14 Verify all electrical connections Switch power ON at the Fu...

Page 7: ... Pulley 48 10 Fan Pulley 24 Fan Pulley 30 Fan Pulley 36 Fan Pulley 42 Fan Pulley 48 11 Fan Shaft 12 Bearing 2 req d 2 Speed Wall Switch 12 Hour Timer REPAIR REPLACEMENT PARTS REPAIR PARTS When ordering repair parts always give the following information 1 Part description 2 Fan model no 3 Fan serial no 10 12 11 8 12 4 2 5 3 7 6 9 1 TO REPOSITION OR REPLACE SPRING A Remove V Belt 8 B Hook spring 6 a...

Page 8: ...tion affixing of any parts or attachments not authorized by Manufacturer or loss of parts In no event shall Manufacturer be liable for any special incidental or consequential damages which may result from any defect in material or workmanship It is expressly understood that Buyer s sole and exclusive remedy shall be repair or replacement of defective parts and that Triangle Engineering shall not b...

Reviews: