THE ENERGY CONSERVATION UNIT (E.C.U.) 

Heat Recovery Unit 

Installation instructions 

Models HR06

 

 
 

Special equipment suggested: 

In addition to the normal tools used by air conditioning technicians, the following should 

be available. A precision thermometer - thermocouple type, a vacuum pump, and a refrigerant recovery unit. 
 

Caution: 

Check each installation in advance. Make sure the air conditioning system is operating within the manufacturer’s 

specifications. Do not proceed until equipment is operating correctly. 

 

 

Note:  The “Uniflow Connector” is actually an Installation Fitting such as 
the IK-5. 

Refrigerant Lines Maximum 

Length (FT) One Way 

Compressor to ECU 

Nominal 

Cooling 

Capacity 

Btu/Hr 

3/8 

O.D. 

1/2 

O.D. 

5/8 

O.D.

3/4 

O.D.

7/8 

O.D.

 

18,000 

20 

40 

24,000 

10 

30 

30,000 

25 

36,000 

15 

50 

42,000 

12 

40 

48,000 

10 

30 

54,000 

25 

40 

60,000 

20 

30 

Note: 

If high pressure switch and/or 

external mufflers are present in the 
discharge line, they should remain in line 
between compressor and ECU. 

1.  Turn off power to water heater (if gas, turn off gas valve), and air conditioning equipment. 

 

2.  Turn off water supply to water heater. 

 

3.  Drain tank if necessary with hot water faucet open. 

 

4.  Locate ECU as close to condensing unit as possible. 

 

5.  Mount unit. Unit should be vertically 

wall mounted

 with tubes down and be 

above the height of the compressor

Never with tubes upward or horizontally pad mounted. 

 

6.  Recover refrigerant charge. Cut hot gas line as close as practical to compressor (before the four way valve on heat 

pumps). Cut openings in condensing unit for hot gas lines. Attach "Gas In" line to compressor discharge line. Attach
"Gas Out" line to other side of cut leading to condenser coil. This unit is designed for heat pump or straight cool 
application.   

Note:

 Hot gas lines and water lines must be insulated with armaflex, rubatex, or similar material. Do not combine 

any lines within the same insulation sleeve or in a chase that may become filled with water. 

 

7.  When refrigerant connections are complete, pressurize system and leak check. Replace or install standard filter 

dryer in liquid line (optional but recommended). Openings in condensing unit must be large enough to pull armaflex 
through, or high temperature grommets installed to prevent contact and abrasion of copper lines. 

 

8.  Evacuate system to remove air and moisture. Recharge to manufacturer's specifications. 

Water Circulating Pump 

Must Be Shut Off Before Charging Begins.

 

 

9.  Connect tubing to "Water In" line of unit. Extend this line to the cold water supply line at the water tank as close to 

the tank as possible. Attach cold water supply with a tee soldered into the line, or a saddle valve of not less than 
5/16” opening. 

Note:

 Less than 50' one way use 1/2" O.D., 50'-90' one way use 5/8" O.D. water lines. 

Summary of Contents for HR06

Page 1: ...ith tubes down and be above the height of the compressor Never with tubes upward or horizontally pad mounted 6 Recover refrigerant charge Cut hot gas line as close as practical to compressor before the four way valve on heat pumps Cut openings in condensing unit for hot gas lines Attach Gas In line to compressor discharge line Attach Gas Out line to other side of cut leading to condenser coil This...

Page 2: ...tric schematic above as a guide Between the ECU and 230v power disconnect run two 2 14 wires with ground in liquid tight cable 13 The piping and wiring are now complete Turn on water to heater With a hot water faucet open allow tank to fill When filled bleed all air from water circuit Loosen plug at center of pump optional to bleed air and verify water to bearings Start the air conditioning unit a...

Page 3: ... solid flow of water is observed c If this measure does not solve the problem check for mechanical damage to the lines d If this check does not provide a solution call your dealer and ask for a serviceman to give the installation a complete technical check 2 If the ECU is circulating but the production is below normal there are two possibilities a If the unit is three or more years old mineral bui...

Page 4: ... products except as authorized by an officer of Trevor Martin Corporation in a signed written document Units not protected against freezing are not warranted LIMITATION OF REMEDY Trevor Martin Corporation will replace or repair at Trevor Martin Corporations option F O B Factory freight prepaid any ECU product defective in workmanship or material if such product is returned to our plant freight pre...

Reviews: