IQVIEW8 Installation Instructions TG201232 Issue 9, 30-May-2017. Applies to v1.30.

IQVIEW8 

Installation Instructions

3

Wire Power Connector

1

Connect Relay Output 

(if required for alarm notification)

230 Vac/24Vac 

transformer 

with isolated 

output (e.g. ACC/24VAC)

General Connections

24 Vac

Some transformers are earthed (grounded) on one side of 

the secondary. If so ensure the earthed (grounded) side is 

connected to the central terminal of the power connector. 

If the polarity of the connection is incorrect the unit will not 

power up. If this happens swap the connections to the right

( ) and central ( ) terminals. 

Terminal size 0.5 to 2.5 

mm

2

 (20 to 14 AWG)

3

2

1

Important: 

Orientate connector 

as shown.

O

I

DO NOT SWITCH ON POWER

Do not connect 230V input 

power to this connector.

WARNING: 

This apparatus must be earthed (grounded) 

via input supply earth (ground) terminal. The earth (ground) 

on this unit is NOT a protective earth (ground), but it is 

essential that an earth is fitted for functional reasons.

Input power supply: 

The 24V supply must include a 

suitably rated switch in close proximity and be clearly 

marked as the disconnecting device for the unit. Do not 

position the equipment so that the disconnecting device 

is difficult to operate.

3.5  Installation - Wiring 

(continued)

3.6  Installation - Connect Cables

Do not connect 230V input 

power to this connector.

SERVICE

13

14

15

16

17

18

19

RS232

24 Vac

1

2

3

A

SER

VICE

6

5

4

Terminal size 0.5 to 2.5 mm

2

 (20 to 14 AWG)

6

5

4

24 Vdc

24 Vac

24 Vac/dc

3

2

1

24 Vdc

24 Vac/dc

3

2

1

0 V

24 Vac ±15% 50/60 Hz at 20 VA minimum

or 24 Vdc 440 mA, 10.5 W. For dc a dc supply with a minimum 

output of 600 mA is recommended.

Note; The required power cannot be provided by a controller’s 

auxiliary supply output; a separate supply is required.

Relay Output Arc Suppression 

Installation Instructions (TG200208)

Arc suppression recommended.

Note: For UL rating the input power connections must be 

made using 18 AWG or larger wire rated at least 90ºC.

For USA/Canada use a UL Listed, 

Class 2, 24 Vac transformer

For USA/Canada use a 

UL Listed, Class 2, 

24 Vac transformer

For USA/Canada use a 

UL Listed, Class 2, 

24 Vac transformer

3     2    1

24 Vac/dc

E

N

L

230 Vac

24 Vac

3     2    1

24 Vac/dc

E    N    L

230 Vac

24 Vac

230 Vac/24 Vac transformer 

with one side earthed 

 

 

 

            (grounded)

Summary of Contents for IQView8

Page 1: ...allation On a Wall 4 3 3 Installation In a Dry Partition Wall 6 3 4 Installation Power up 8 3 5 Installation Wiring 9 3 6 Installation Connect Cables 10 4 End User Licence Agreement 12 5 Cleaning and...

Page 2: ...PARTITION WALL BOX In Wall Mounting Important Keep connectors Operating Altitude 2000 m 6562 Panel Mounting Surface Mounting In Wall Mounting Go to step 6 on page 3 Go to section 3 2 page 4 Go to sect...

Page 3: ...ectors 9 Connect Cables 10 Close Panel 3 1 Installation Mounting continued 4 3 1 2 Click 2 to 5mm 0 08 to 0 2 213 mm 8 38 148 mm 5 82 Cutout for display Follow Installation Wiring on page 9 175 mm 6 8...

Page 4: ...repare Mounting Holes for flat surface and UK US double pattress mounting 3 2 Installation On a Wall Requires IQVIEW8 SURFACE MOUNTING BOX sold separately 22 mm 0 87 Either UK Double Pattress Box Or U...

Page 5: ...nsert top 2 screws 3 mm 0 12 Either UK Double Pattress Box Or US Double Pattress Box Then for flat surface and UK US double pattress box Either Using Drill outs If routing cables through the drill out...

Page 6: ...EW8 10 Fit Access Lid 3 2 Installation On a Wall continued Click 9 5 to 25 mm 0 35 to 0 98 3 3 Installation In a Dry Partition Wall Requires IQVIEW8 DRY PARTITION WALL BOX sold separately 55 mm 2 17 2...

Page 7: ...4 places Loosen locking screws Adjust brackets 4 places Tighten adjustment screws Tighten locking fixing screws 4 places 4 places 3 3 Installation In a Dry Partition Wall continued Either into Rear of...

Page 8: ...3 3 Installation In a Dry Partition Wall continued 3 4 Installation Power up Normal Operation Fault Power Orange Check power supply Read and agree to the end user licence agreement see section 4 O I...

Page 9: ...1000 m 1090 yds 700 m 765 yds 350 m 380 yds 2 Trend TP 2 2 22 HF 200 Belden 8723 1000 m 1090 yds 1000 m 1090 yds 500 m 545 yds 250 m 270 yds 4 2 wire X T T R R 10 9 8 7 RX RX TX TX 4 wire X T T R R T...

Page 10: ...a suitably rated switch in close proximity and be clearly marked as the disconnecting device for the unit Do not position the equipment so that the disconnecting device is difficult to operate 3 5 In...

Page 11: ...2 3 A SERVICE 6 5 4 10 9 8 7 RS232 24 Vac 1 2 3 A Either Ethernet Or Current Loop RJ45 100 m 109 yds RJ45 Or RS232 RS23 2 24 Vac A SERVICE 13 14 15 16 17 18 19 RS232 24 Vac 1 2 3 A SERVICE 13 14 15 16...

Page 12: ...RISK AS TO SATISFACTORY QUALITY PERFORMANCE ACCURACY AND EFFORT INCLUDING LACK OF NEGLIGENCE IS WITH YOU ALSO THERE IS NO WARRANTY AGAINST INTERFERENCE WITH YOUR ENJOYMENT OF THE SOFTWARE OR AGAINST...

Reviews: