IQVIEW8 Installation Instructions TG201232 Issue 9, 30-May-2017. Applies to v1.30. 9
Installation Instructions IQVIEW8
1
Wire Relay Connector
(if required for alarm notification)
2
Wire Current Loop
(if required for network connection)
3.5 Installation - Wiring
On when Alarm not present (Relay off)
On when Alarm present (Relay energised)
Cable
1k2
baud
4k8
baud
9k6
baud
19k2
baud
No. of
Wires
Belden 9182
1000 m
(1090
yds)
1000 m
(1090
yds)
1000 m
(1090
yds)
700 m
(765
yds)
2
Belden 9207
1000 m
(1090
yds)
1000 m
(1090
yds)
1000 m
(1090
yds)
500 m
(545
yds)
2
Trend
TP/1/1/22/
HF/200
(Belden 8761)
1000 m
(1090
yds)
1000 m
(1090
yds)
700 m
(765
yds)
350 m
(380
yds)
2
Trend
TP/2/2/22/
HF/200
(Belden 8723)
1000 m
(1090
yds)
1000 m
(1090
yds)
500 m
(545
yds)
250 m
(270
yds)
4
2 wire
X
T
T
R
R
10
9
8
7
RX+ RX-
TX+
TX-
4 wire
X
T
T
R
R
T
T
R
R
10
9
8
7
RX+ RX-
TX+
TX-
Important:
Orientate connector
as shown.
Terminal size 0.5 to 2.5
mm
2
(20 to 14 AWG)
AC rating: 60 VA. e.g 30 Vac max @ 2 A, 24 Vac @2.5 A
DC rating: 60 W. e.g. 40 Vdc max @ 1.5 A, 24 Vdc @ 2.5 A
5
4
6
Do not connect 230V input
power to this connector.
Relay Output Arc Suppression
Installation Instructions (TG200208)
Arc suppression recommended.
Note: For UL rating CU only cable must be used.
Important:
Orientate connector
as shown.
Polarity independent
Terminal size 0.5 to 2.5
mm
2
(20 to 14 AWG)
10
9
8
7
+
-
6
5
4
C
NO
NC
24
Va
c
Po
w
er
Sup
pl
y
Load
+
-
6
5
4
C
NO
NC
24
Va
c
Po
w
er
Sup
pl
y
Load