IQ4E/.. Installation Instructions - Mounting TG201338 Issue 4, 19-Jan-2016. Applies to v3.33. 9
Installation Instructions - Mounting IQ4E/..
14
Connect Wallbus
(if required)
80
81
WMB
e.g RD-WMB
3 INsTAllATIoN
(continued)
Terminal size:
0.14 to 2.5 mm
2
(22 to 12 AWG).
Terminal screw torque: 0.45 to 0.62 Nm (4 to 5.5 lb.in).
Cable type:
Unscreened twisted pair.
Maximum cable length: 60 m (200 ft) in total, used to connect
all wallbus devices.
Number of Devices:
up to 14 (subject to power loading -
refer to device documentation).
Example wiring
Polarity independent
to additional
wallbus devices
IQ4 Configuration Manual
(TE201263)
IQ4E
IQ4E