TREND IQ4E Installation Instructions Manual Download Page 10

10 

IQ4E/.. Installation Instructions - Mounting TG201338 Issue 4, 19-Jan-2016. Applies to v3.33.

IQ4E/.. 

Installation Instructions - Mounting

15

Install and Connect I/o Modules 

(if required)

IQ4E  is  compatible  with  I/O  modules  from  the  IQ4/IO  and 

XCITE/IO ranges. Depending on the controller variant, up to 

192 I/O channels are supported (including 16 channels on the 

IQ4E).

3 INsTAllATIoN 

(continued)

IQ4E/.. Data Sheet (TA201340)

IQ4/IO

IQ4/IO

IQ4/IO

IQ4/IO

IQ4/IO

IQ4E/..

XCITE/IO XCITE/IO

XCITE/IO

IQ4/IC/lINK

interconnectors

IQ4/IC/ADPT

cable adapter

xCITE/CC

cable adapter

xCITE/IC

interconnector

IQ4/IC/TERM

terminator

xCITE/TERM

terminator

Connecting I/o modules to the IQ4E I/o bus

IQ4/IC/ADPT

cable adapter

cable

interconnections

Remove I/O bus terminator from IQ4E and retain for use on the last IQ4/IO module (see below)

Maximum I/o bus length 

(excluding rigid interconnectors)

Maximum number of I/o modules on I/o bus

IQ4/IO Installation Instructions

- Mounting (TG201338)

XCITE/IO Installation Instructions

- Mounting (TG200627)

cable

interconnection

xCITE/CC

cable adapter

IQ4/IC/ADPT

cable adapter

Up to 30 modules can be connected to the I/O bus, depending 

on the configuration of controller and modules used:

Product Configuration

Maximum  

No. of Modules

IQ4E controller with  

IQ4/IO modules only

30

Any combination using XCITE/IO 

modules or IQ3XCITE controller

15

Note: Check that the controller supports the required number 

of I/O channels.

Product Configuration

Cable Type

Belden 3084A Belden 7895A

IQ4E controller with  

IQ4/IO modules only

total bus length 

up to 100 m 

(109 yards)

total bus length 

up to 300 m 

(328 yards)

Any other combination 

using XCITE/IO modules 

or IQ3XCITE controller

total bus length

up to 30 m (33 yards)*

*Maximum 10 m (11 yards) for certain system configurations - 

for details check the XCITE/IO Modules Data Sheet (TA201352) 

and XCITE/IO Installation Instructions - Mounting (TG200627).

Summary of Contents for IQ4E

Page 1: ...reinforced insulation 3 Installation 1 Box Contents 2 Storing Contents 1 Box Contents 1 2 Storing 1 3 Installation 1 Note For temperatures below 0 C 32 F special care must be taken that there is no co...

Page 2: ...tinued Must be installed in an enclosure rated to at least IP20 or equivalent Note For temperatures below 0 C 32 F special care must be taken that there is no condensation on or within the unit Protec...

Page 3: ...structions Mounting IQ4E 3 Mount Unit on DIN Rail 4 Attach large Barcode label to Panel 5 open Rotating Covers 3 INsTAllATIoN continued I QECO Q3 B_ X7 3 0 8 0 0 3 1 SERIAL No IQ4e Q3B_X73080031 TREND...

Page 4: ...0 C or greater This equipment must be earthed grounded 230 230 Vac 10 50 60 Hz at up to 70 VA The 230 V supply must include a dedicated 5 A fuse complying with IEC60269 BS1362 and a suitably rated swi...

Page 5: ...5 lb in TP 1 1 22 HF 200 Belden 8761 cable recommended for all inputs outputs Screened cable is not generally required unless the cable passes through electrically noisy environments Where it is used...

Page 6: ...equired 11 Connect Auxiliary Supply Output s if required 3 Installation continued Output voltage 0 to 10 Vdc Maximum current 20 mA source 3mA sink Output voltage 24 Vdc 5 Maximum current Terminals 70...

Page 7: ...ystem 4 wire system T R T R T R T R panel enclosure ground T R R X T Terminal size 0 14 to 2 5 mm2 22 to 12 AWG Terminal screw torque 0 45 to 0 62 Nm 4 to 5 5 lb in Maximum cable length depends on cab...

Page 8: ...nnection to an RS 485 4 wire system a suitable 2 to 4 wire converter will be required RS 232 system RJ12 FFC68 Plug Local Supervisor Port 1 RX 2 NC 3 CTS 4 RTS 5 GND 6 TX TX RX RTS CTS GND pin 1 Note...

Page 9: ...d Terminal size 0 14 to 2 5 mm2 22 to 12 AWG Terminal screw torque 0 45 to 0 62 Nm 4 to 5 5 lb in Cable type Unscreened twisted pair Maximum cable length 60 m 200 ft in total used to connect all wallb...

Page 10: ...rigid interconnectors Maximum number of I O modules on I O bus IQ4 IO Installation Instructions Mounting TG201338 XCITE IO Installation Instructions Mounting TG200627 cable interconnection XCITE CC c...

Page 11: ...ose Rotating Covers 17 Close Panel Enclosure 18 Configure IQ4E Controller and I O Modules 1 Remove from DIN rail 3 INsTAllATIoN continued IQ4E Installation Instructions Configuring TG201339 IQ4 IO Ins...

Page 12: ...end Control Systems Ltd s software suppliers HAS RELIED UPON Trend Control Systems Ltd TO CONDUCT SUFFICIENT TESTING TO DETERMINE THAT THE SOFTWARE IS SUITABLE FOR SUCH USE NO WARRANTIES FOR THE SOFTW...