IQ4E/.. Installation Instructions - Mounting TG201338 Issue 4, 19-Jan-2016. Applies to v3.33. 7

Installation Instructions - Mounting IQ4E/..

12

Connect Trend Current loop Network 

(/LAN variants only, if required)

3 INsTAllATIoN 

(continued)

T R

T R

T R

T R

panel/enclosure 

ground

additional terminals

T

R

R

X

T

R

R

T

T

additional terminals

If  the  current  loop  is  enabled 

(default), the LAN communications 

will not operate without an intact 

network. If a network is not fitted a 

loop back must be fitted as shown.

Not connected

2 wire system

4 wire system

T R

T R

T R

T R

panel/enclosure 

ground

T

R

R

X

T

Terminal size:  

0.14 to 2.5 mm

2

 (22 to 12 AWG).

Terminal screw torque: 0.45 to 0.62 Nm (4 to 5.5 lb.in).

Maximum cable length depends on cable type and baud rate:

Cable

Type

Baud Rate

1k2 4k8 9k6 19k2 38k4 76k8

Trend 

TP/2/2/22/

HF/200

Belden 8723

Shielded 

twisted pair

2 pairs (4 

conductors)

1000 m

(1090 yds)

700 m

(765 

yds)

350 m

(380 

yds)

175 m

(191 

yds)

Trend 

TP/1/1/22/

HF/200

Belden 8761

Shielded 

twisted pair

1 pair (2 

conductors)

Belden 9182

Belden 9207

Twinaxial (2 

conductors)

Note: Adjacent devices may specify different maximum cable 

lengths and baud rates. The shortest cable length (for the chosen 

baud rate) applies when connecting to the IQ4E current loop.

Summary of Contents for IQ4E

Page 1: ...reinforced insulation 3 Installation 1 Box Contents 2 Storing Contents 1 Box Contents 1 2 Storing 1 3 Installation 1 Note For temperatures below 0 C 32 F special care must be taken that there is no co...

Page 2: ...tinued Must be installed in an enclosure rated to at least IP20 or equivalent Note For temperatures below 0 C 32 F special care must be taken that there is no condensation on or within the unit Protec...

Page 3: ...structions Mounting IQ4E 3 Mount Unit on DIN Rail 4 Attach large Barcode label to Panel 5 open Rotating Covers 3 INsTAllATIoN continued I QECO Q3 B_ X7 3 0 8 0 0 3 1 SERIAL No IQ4e Q3B_X73080031 TREND...

Page 4: ...0 C or greater This equipment must be earthed grounded 230 230 Vac 10 50 60 Hz at up to 70 VA The 230 V supply must include a dedicated 5 A fuse complying with IEC60269 BS1362 and a suitably rated swi...

Page 5: ...5 lb in TP 1 1 22 HF 200 Belden 8761 cable recommended for all inputs outputs Screened cable is not generally required unless the cable passes through electrically noisy environments Where it is used...

Page 6: ...equired 11 Connect Auxiliary Supply Output s if required 3 Installation continued Output voltage 0 to 10 Vdc Maximum current 20 mA source 3mA sink Output voltage 24 Vdc 5 Maximum current Terminals 70...

Page 7: ...ystem 4 wire system T R T R T R T R panel enclosure ground T R R X T Terminal size 0 14 to 2 5 mm2 22 to 12 AWG Terminal screw torque 0 45 to 0 62 Nm 4 to 5 5 lb in Maximum cable length depends on cab...

Page 8: ...nnection to an RS 485 4 wire system a suitable 2 to 4 wire converter will be required RS 232 system RJ12 FFC68 Plug Local Supervisor Port 1 RX 2 NC 3 CTS 4 RTS 5 GND 6 TX TX RX RTS CTS GND pin 1 Note...

Page 9: ...d Terminal size 0 14 to 2 5 mm2 22 to 12 AWG Terminal screw torque 0 45 to 0 62 Nm 4 to 5 5 lb in Cable type Unscreened twisted pair Maximum cable length 60 m 200 ft in total used to connect all wallb...

Page 10: ...rigid interconnectors Maximum number of I O modules on I O bus IQ4 IO Installation Instructions Mounting TG201338 XCITE IO Installation Instructions Mounting TG200627 cable interconnection XCITE CC c...

Page 11: ...ose Rotating Covers 17 Close Panel Enclosure 18 Configure IQ4E Controller and I O Modules 1 Remove from DIN rail 3 INsTAllATIoN continued IQ4E Installation Instructions Configuring TG201339 IQ4 IO Ins...

Page 12: ...end Control Systems Ltd s software suppliers HAS RELIED UPON Trend Control Systems Ltd TO CONDUCT SUFFICIENT TESTING TO DETERMINE THAT THE SOFTWARE IS SUITABLE FOR SUCH USE NO WARRANTIES FOR THE SOFTW...

Reviews: