background image

Page 12 

IT-400 series instruction manual 

ENGLISH 

10.0.  PROGRAMMING 

With the control panel in maintenance mode it is possible to program it using dip-switches A 
and B as listed below: 

DIP-SWITCH A  -  OPTIONS

                                      

 

1

     

ON

 = Sets control panel in maintenance mode.   

OFF

 = Sets normal functioning. 

2     

ON

 = Exit time 60 sec.  

OFF

 = Exit time 30 sec. 

3 - 4   

Entrance time Zone 1

 

 OFF- 

OFF 

=   Immediate 

 

OFF- ON  

=   Entrance time: 15 sec.                                                              

 

ON-OFF   

=   Entrance time: 30 sec. 

 

ON-ON     

=   Entrance time: 60 sec. 

5 - 6  

Entrance time Zone 2

 

 OFF-OFF 

 

= Immediate 

 OFF-ON 

 

=   Entrance time:  15 sec. 

 

ON-OFF

    =   Entrance time: 30 sec 

            

ON-ON      

=   Entrance time: 60 sec 

7       

Automatic zone exclusion after 4 alarm cycles

  - 

OFF

 = NO ; 

ON

 = YES 

8

       

Silent or audible panic  

-

  

OFF

 = silent ; 

ON

 = audible 

 
DIP-SWITCH B  -  OPTIONS

 

1     

ON

    =   Fire relay follows the timing of the indoor siren 

           

OFF

   =   Fire relay blocks only when the control panel is disarmed (DAY) 

2    

ON

    =   External siren has only one alarm cycle 

           

OFF

   =   External siren completes all alarm cycles 

3 - 4  

Indoor siren alarm time

   

 

            

OFF-OFF  

=   Persistent sound  

            

OFF-ON    

=   Alarm time:  1 min. 

            

ON-OFF    

=   Alarm time:  2 min. 

             

ON-ON      

=   Alarm time:  3 min. 

5 - 6 

  

External siren alarm time (never more than that programmed on the indoor siren) 

            

OFF-OFF

  =   Persistent sound  

            

OFF-ON    

=   Alarm time:  1 min. 

            

ON-OFF    

=   Alarm time:  2 min. 

            

ON-ON      

=   Alarm time:  3 min. 

7 - 8      

Programming of lines L1-L2-L3-L4 (burglary) and L6-L7-L8 (fire, hold-up and tamper)

 

 

OFF-OFF  

=   All lines disabled 

 

OFF-ON    

=   Lines normally closed  NC 

 

ON-OFF    

=   Balanced lines (end of line resistor 4K7 Ohm necessary) 

 

ON-ON      

=

   NOT USE

 

 

At the end of programming, close the cover of the control panel making sure that dip 1 
of dip-switch A is in OFF position (normal function) and that the tamper button is closed. 

Page 9 

IT-400 series instruction manual 

ENGLISH 

ATTENTION 

For the alarm to be triggered the line must remain open for more then 0,3 seconds.

 

  

 

6.0. ZONE DESCRIPTION 

The series IT-400 control panels (It-400, IT-400 K, IT-400 D) have 7 zones in total of which L1

 L4

 

 are burglary alarm zones and L6, L7, L8 are Fire, panic and anti-sabotage. 

 

All 7 zones (Terminals 18 to 23 and 25 to 29) can be programmed through the dip-switch 
as 

normally closed 

(NC) or 

balanced 

with end of line resistance 4.7 K ohm. 

 

The first 2 burglary zones,

 

L1

 L2

 

(Terminals 18,19,20)

 

may be programmed either as  

delayed 

or 

immediate

, while L3

 L4

  

(Terminals 21,22,23) are 

only immediate

 

The remaining 3 zones, anti-sabotage, fire and hold-up (Terminals 23,24,25,26,27,28,29) 

 are 

always active

 

ATTENTION 

If the control panel is programmed using end of line resistors you 
must  place  a  resistor  of    4.7  K  ohm  in  series  with  the  sensors             
installed. If the value of this resistor is changed (for example short  
circuit), the panel will trigger an alarm. 

Note the location of 4K7 
end of line resistor (see 
the figure on the right).   

6.1.   BALANCE RESISTOR CONNECTION 

Control Panel 

Sensor 

 Alarm output 

zone (NC) 

Balanced line 

R = 4.7 K ohm 

7.0. KEY 

The IT-400 / IT-400 K may be armed and disarmed through the key situated on the front panel, 
or with a code made of up to 6 digits (IT-400 D only). Remote arming is possible through     
remote electronic key (optional available only for IT-400K that incorporates on board the     
electronic key interface) or you may use any form of NC key switch with IT-400 and IT400 D.

 

Summary of Contents for IT-400

Page 1: ...indicates control panel armed day position This is located on the remote electronic key base see page 10 36 Output for remote LED that indicates alarm memory This is located on the remote electronic...

Page 2: ...relay alarm outputs Separate relay alarm outputs for internal sirens Remote indication for unit ON Low battery indication Output for siren with or without battery back up Relay output for panic an fi...

Page 3: ...mains fuse and if the battery charger is functioning correctly 13 8 Vdc on cables of battery If all functions correctly then the battery must be replaced Please dispose of faulty batteries in an envir...

Page 4: ...C Outdoor siren relay 33 Buzz Remote Key Impulse Remote Key ON OFF Page 17 IT 400 series instruction manual ENGLISH To disarm the panel IT 400 Rotate the key in DAY position IT 400 K Insert the key in...

Page 5: ...e will cause Flashing of the corresponding LED on the front panel until the control panel is re armed to signal Alarm memory Lighting of the DAY LED on the front panel and on receptacle of electronic...

Page 6: ...g the exit time the following will take place The ON LED on the panel and electronic key receptacle will light If however there are zones open or unbalanced the LED of the triggered zone on the panel...

Page 7: ...the control panel to DAY mode 13 0 BY PASSING ZONES It is possible to partially arm the system NIGHT mode by by passing some of the zones NOTE The control panel is supplied with all the zones active P...

Page 8: ...ight 1 Off signals line closed normal status 2 Flashing indicates zone in alarm or alarm memory L BAT FIRE PANIC AS POWER L BAT FIRE PANIC AS POWER L1 L2 L3 L4 L1 L2 L3 L4 D C A B ON DAY ON NIGHT DAY...

Page 9: ...the cover of the control panel making sure that dip 1 of dip switch A is in OFF position normal function and that the tamper button is closed Page 9 IT 400 series instruction manual ENGLISH ATTENTION...

Page 10: ...0 K to the terminals on the back side of the receptacle as shown in the figure on the right Control panel armed ON Control panel armed Night Remote receptacle Electronic key Control panel disarmed DAY...

Reviews: