Page 4
IT-400 series instruction manual
ENGLISH
Manutenzione
Per passare da …..
3.0. TERMINAL BLOCK CONNECTIONS
1 2
-
Auxiliary output 12 Vdc -
(Imax 1 A)
.
This output is always active with control panel armed or disarmed
.
3 4 5
-
Normally opened (N.O.) - Common (C) - Normally closed (N.C.) - Volt free relay
contact for fire / gas alarm (Imax 8 Amp).This relay is activated for the programmed
time when the zone L6 is triggered.
6 7 8
-
Normally closed (N.C.) - Normally opened (N.O.) - Common (C)
Volt free panic alarm relay -
(Imax 1 A)
.
This relay activates for 10 sec. At the opening of line L7 (panic audible / non
audible).
9 10 11 -
Volt free change-over relay alarm output for
internal siren
-
(Imax 8 A)
.
Normally opened (N.O.) - Common (C) - Normally closed (N.C.).
This relay is activated if burglary, sabotage, or audible panic alarms are
triggered.
12 13 14 -
Volt free change-over relay alarm output for
external siren
-
(Imax 8 A)
.
Normally closed (N.C.) - Normally opened (N.O.) - Common (C.).
This relay is activated if burglary, sabotage, or audible panic alarms are
triggered.
Bridging the connector TS1 as shown above, the common of the relay
(Terminal 14) is connected to +12 Vdc.
15 16 17 -
Volt free change-over relay alarm output for
external siren
-
(Imax 8 A)
.
Normally opened (N.O.) - Common (C) - Normally closed (N.C.).
This relay is activated if burglary, sabotage, or audible panic alarms are triggered.
TS1
Volt free relay contacts
+ 12 Vdc to Terminal 14
Normally operation
Reset factory condition
F1 = 1 A
PC board
protection
F2 = 1 A
Auxiliary ou-
tputs protection
F3 = 1 A
Battery polarity
inversion
ON
OFF
12345678
Dip-switch A
12345678
Dip-switch B
J8
F4 = 1 A
Short circuit
transformer
43
42
41
40
39
38
37
36
35
34
1 2 3 4 5 6 7 8 9 10 11
12 Vdc auxiliary output
Fire alarm relay
Panic alarm relay
Indoor siren relay
NO C NC NC NO C NO C NC
30 31 32
L1 L2
L3 L4
Bus
RS485
L5 L6
L7 L8
Relay with selectable operation
12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
Negative
L5 = Not used
L6 = Fire alarm line
L7
=
Panic alarm line
L8 = 24 hours antitamper line
19 Vac
GND
19 Vac
Unit ON
Negative impulse
D
C
B
A
IT–400 / 400D version
GND
TX
RX
35
34
Normally closed lines
(NC)
Remote key
(NC)
Volt free relay contacts
NC NA C NO C NC
Outdoor siren relay
33
Buzz
Remote Key Impulse
Remote Key ON/OFF
Page 17
IT-400 series instruction manual
ENGLISH
To disarm the panel
:
IT-400 : Rotate the key in “
DAY
” position.
IT-400 K : Insert the key into the key holder for less than 5 sec.
IT-400 D : Digit the access code on a keypad and press “
#
”.
The panel will disarm
. The LED “
ON
” or “
NIGHT
” will
go off
.
If while armed, an alarm has been triggered, when the control panel is disarmed, the LED
of the triggered zone will flash until the control panel is again armed. This indicates "Alarm
memory".
To cancel the alarm memory in IT-400 D / IT-400K, press any key on the keypad or change
the status of the control panel by first arming and then disarming the control panel.
To cancel the alarm memory in IT-400, it is sufficient to change the status of the control
panel by rotating the key before in "
ON
" position and then in "
DAY
" position.
16.0. DISARMING
(DAY mode)
1)
The unbalancing of the 24 hour zone (Terminals 28 and 29), the sabotage of zones L1
L4
and the inserting of false electronic keys will cause
:
- Slow flashing of “
24 H
” LED on the panel. The LEDs will remain active until the next
arming of the panel to indicate “Alarm memory”.
- The activation of the indoor and outdoor siren alarm relays (Terminals
9 to 17) for the
time that has been programmed.
2)
The unbalancing of the fire zone (Terminals 25 and 26) causes
:
- Slow flashing of the “
FIRE
” LED on the panel. The LEDs remain active until the next
arming of the panel to indicate “Alarm memory”.
- The activation of the fire alarm relay (Terminals 3, 4 and 5) for 30 seconds.
3)
The unbalancing of the panic zone (Terminals 27 and 28) causes
:
- Slow flashing of the ”
PANIC
” LED on the panel. The LEDs remain active until the next
arming of the panel to indicate “Alarm memory”.
- The activation of the panic alarm relay (Terminals 5, 6 and 7) for 10 seconds.
- The activation of the indoor and outdoor siren alarm relays (Terminals 9 to 17) for the
time they have been programmed.
4)
Low battery level (load under 10.5 V) causes
:
- Slow flashing of the “
LOW B.
” LED on the panel. The LED remain active until the next
arming of the panel to indicate “Alarm memory”.
5)
Opening of L1
L4 when functioning in N.C. or the violation of the zones (both not
excluded) will cause
:
- The lighting of the LED on the panel corresponding to the triggered zone only for the
time that the zone remains open or unbalanced.