![Travis Industries Small Flush Owner'S Manual Download Page 42](http://html.mh-extra.com/html/travis-industries/small-flush/small-flush_owners-manual_1154140042.webp)
42 Listing
Label
© Travis Industries
100-01342
4131101
Listing Label
DO NOT REMOVE THIS LABEL
CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT INSTALLATION AND RESTRICTIONS IN YOUR AREA.
SUITABLE FOR USE IN FACTORY-BUILT (Z.C.) FIREPLACES AND MASONRY FIREPLACES.
Report No.
100517991PRT-001
Control No. 4000515
MODEL:
SMALL FLUSH WOOD
with Hybrid-Fyre™
Certified for USA and Canada
SERIAL NO:
CONFORMS TO UL STD 1482; CERTIFIED TO ULC STD S628-1993
FACTORY-BUILT (Z.C.) FIREPLACE OR MASONRY FIREPLACE INSTALLATION
INSERT
A
F
B
D
C
E
HEARTH EXTENSION
MANTEL
COMBUSTUBLE SIDEW
ALL
COMBUSTIBLE F
ACING
NON-COMBUSTIBLE
FIREPLACE FACING
Minimum Clearance to
Combustibles and Hearth
Requirements
Masonry
Fireplace
Installations
Factory-Built
(Z.C.) Fireplace
Installations
A.
B.
*C.
*D.
*E. (US)
*E. (CAN)
F. (US)
F. (CAN)
11.625 in. / 296 mm
6.25 in. / 159 mm
37.5 in. / 953 mm
37.5 in. / 953 mm
16 in. / 407 mm
18 in. / 458 mm
6 in. / 153 mm
8 in. / 204 mm
11.625 in. / 296 mm
6.25 in. / 159 mm
37.5 in. / 953 mm
37.5 in. / 953 mm
16 in. / 407 mm
18 in. / 458 mm
6 in. / 153 mm
8 in. / 204 mm
* From the base of Fireplace Insert.
Factory-Built (Z.C.) Fireplace installations require a fireplace chimney full re-line. Factory-Built (Z.C.) Fireplace chimney must have a minimum
cross-sectional area of 28.85 square inches / 733 square mm. A non-combustible hearth floor protection is also required that provides a thermal
resistance with an R value equal to 1.19 or greater (see chart above and / or owner’s manual for required sizing details).
Minimum 6 in. / 153 mm diameter Stainless Steel liner, full re-line required.
In Canada; a fireplace insert shall be installed with a continuous chimney liner extending from the fireplace insert to the top of the chimney. A
chimney liner shall be tested for conformance with Class 3 requirements of CAN/ULC-S635, Standard for Lining Systems for Existing Masonry or
Factory-Built Chimneys and Vents, or CAN/ULC-S640, Standard for Lining Systems for New Masonry Chimneys.
PREVENT HOUSE FIRES - Install and use only in accordance with the manufacturer’s installation and operating instructions. Contact your local
building or fire officials about restrictions and installation inspection in your area. Do not connect this unit to a chimney flue serving another
appliance.
This wood heater contains a catalytic combustor, which needs periodic inspection and replacement for proper operation. Consult owner’s manual
for further information. It is against the law to operate this wood heater in a manner inconsistent with operating instructions in the owner’s
manual, or if the catalytic element is deactivated or removed. CAUTION: the combustor used in this appliance (part no. 174-01111) is fragile and
must be handled carefully. Burning of metal foils, plastic, garbage, sulphur and diesel oil will render the catalyst in the combustor inactive. The
performance and durability of the catalytic combustor has not been evaluated as part of the certification.
Electrical Rating:
Blowers:
115V., 60 Hz, 1.8 Amps
# 228-10069 / 228-10070
Replace glass only with 5mm neoceramic or
ceramic glass.
Do not route power cord under or in front of appliance.
TRAVIS INDUSTRIES, INC.
4800 Harbour Pointe Blvd. SW
Mukilteo, WA 98275
Manufactured by:
www.travisproducts.com
U.S. ENVIRONMENTAL PROTECTION AGENCY
Certified to comply with July 1990 particulate emission standards.
Made in U.S.A.
2013
2014
2015
2016
Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
Oct
Nov
Dec
DATE OF MANUFACTURE
1049