10 Fireplace
Insert
Installation
(for qualified installers only)
© Travis Industries
100-01342
4131101
Hearth Requirements
When installing into a masonry fireplace, the hearth must meet Uniform Building Code (UBC) standards.
USA
When installing into a zero-clearance fireplace, the hearth must extend 16” (407mm) to the front and 8”
(204mm) to the sides of the insert. The hearth must provide an R-value (thermal resistance) of 1.19 or
greater.
If the insert is a minimum 2” (51mm) above the combustible floor (carpet, wood, etc.) the hearth must
extend 16” (407mm) in front and 8” (204mm) on both sides of the insert. Hearth must be non-combustible
(cement board, tile, etc.). No R-value (thermal resistance) is required.
CANADA
When installing into a zero-clearance fireplace, the hearth must extend 18” (458mm) to the front and 8”
(204mm) to the sides of the insert. The hearth must provide an R-value (thermal resistance) of 1.19 or
greater.
If the insert is a minimum 2” (51mm) above the combustible floor (carpet, wood, etc.) the hearth must
extend 18” (458mm) in front and 8” (204mm) on both sides of the insert. Hearth must be non-combustible
(cement board, tile, etc.). No R-value (thermal resistance) is required.
Non-Combustible Hearth
(min. R-Value 1.19)
Combustible
Flooring
Non-Combustible Spark Protection
(Tile, Cement Board, Steel, etc.)
USA Min. 16" (407mm)
Canada Min. 18" (458mm)
Combustible
Flooring
Min. 2"
(51mm)
USA Min. 16" (407mm)
Canada Min. 18" (458mm)