Stove Installation
(for qualified installers only)
13
© Travis Industries
100-01164
4041115
Mobile Home Requirements
•
Outside air must be installed - see "Outside Air Requirements" on page 11
•
Chimney connector and chimney must be one of the following types:
AMERI-TEC model DCC with model HS chimney
DURAVENT model DVL with DURATEC or DURA-PLUS chimney
I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector
METALFAB model DW connector with TG chimney
SECURITY model DP connector with SECURITY model ASHT or S2100 chimney
Standard Masonry Chimney with any one of the above listed connectors
NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter may be required.
•
Stove placement must maintain the following clearances to combustibles (drywall, furniture, etc.)
AAAAAA
AAAAAA
AAAAAA
AAAAAA
AAAAAA
AAAAAA
a
b
f
AAAAAA
AAAAAA
AAAAAA
AAAAAA
AAAAAA
AAAAAA
c
Measure all clearances from the
nearest edge of the stove top.
d
e
c
Rear heat
shield
Figure 8
Minimum Clearance
(See the illustration above)
Reduced Clearance
Connector
A
Sidewall to stove
16"
B
Backwall to stove
10"
C
Cornerwall to stove
7-1/2"
D
Connector to sidewall
27-1/2"
E
Connector to backwall
12-3/4"
F
Connector to cornerwall
18-1/2"
•
If using offsets, use the connector clearance listed in Figure 9,
not the connector manufacturer's clearance
.
•
The appliance must be secured to the floor (consult your
building official). Secure the outside air boot to the floor and
stove to insure the stove does not dislocate.
•
Mobile home installations require a spark arrester at the
chimney termination.
•
The appliance must be grounded to the chassis of the mobile
home (consult your building official).
•
WARNING:DO NOT INSTALL IN SLEEPING ROOM.
•
CAUTION:THE STRUCTURAL INTEGRITY OF THE MOBILE
HOME FLOOR, WALL, AND CEILING/ROOF MUST BE
MAINTAINED.
Minimum Stove
Clearance
(as outlined above)
AAAAA
12” Min.
Minimum Connector
Clearance
(as outlined above)
AA
AA
Figure 9