background image

TRANE

®

Coil / Condenser Cleaning

12

Coil Fins and External

Surface Cleaning

Coils should be kept clean to maintain
maximum performance.  For operation
at its highest efficiency, the refrigerant
coil should be cleaned often during
periods of high cooling demand or
when dirty conditions prevail.  A routine
cleaning schedule (minimum of once
per year) is recommended to prevent
dirt buildup in the coil fins, where it may
not be visible.

Remove large debris from the coils and
straighten fins before cleaning.
Remove filters before cleaning.

Clean refrigerant coils with cold water
and detergent, or with one of the
commercially available chemical coil
cleaners.  Rinse coils throughly after
cleaning.

Mechanical Cleaning of

Condenser

The mechanical method of cleaning
the condenser is used for removing
mud and other loose material from the
condenser.  Complete the following:
1. Turn off condenser supply water.
2. Remove condenser end plates by

removing clamp bolts.  This
exposes the condenser tubes.

3. Rotate a round brush through the

tubes to loosen contaminant.

4. Flush tubes with water which will

flush the sludge out through the
drain opening in the bottom of the
supply header and the drain
opening in the return pipe.

5. Replace condenser end-plates and

clamps.  The end-plates must be
centered when the clamp is
tightened.

6. Replace coil headers with gaskets

and torque bolts to 50 ft-lbs.

Chemical Cleaning of

Condenser

Chemical cleaning removes scale
deposits built up by minerals in the
water.  For a suitable chemical
solution, consult a water treatment
specialist.  The condenser water circuit
is composed of copper, steel, and cast
iron.

See Figure 5 for a typical piping
arrangement for chemically cleaning
the condenser.  All materials used in
the external circulating system, along
with the quantity of  cleaning material,
duration of cleaning time and safety
precautions necessary for handling the
cleaning agent, should be provided or
approved by the chemical supply
house.

Caution: Do not clean the refrigerant
coil with hot water or steam.  The use
of hot water or steam as a refrigerant
coil cleaning agent will cause high
pressure inside the coil tubing and
subsequent damage to the coil.

Caution: Do not use acidic chemical
coil cleaners.  Do not use alkaline
chemical coil cleaners that, after
mixing have a pH value greater than
8.5, without also using an aluminium
corrosion inhibitor in the cleaning
solution.  If these instructions are
followed, the unit could be damaged.

WARNING: Some chemical coil-
cleaning compounds are caustic or
toxic.  Use these substances only in
accordance with the manufacturer

s

instructions Failure to do so may
result in injury, death or equipment
damage.

Caution: Failure to properly drain
and vent coils when not in use during
freezing temperatures may result in
coil freeze-up damage.

Caution: Failure to provide adequate
water treatment in condenser
systems may result in fouling of the
coil and condenser surfaces or
undue metal damage.

Condenser Cleaning

Condensing water contains minerals
that collect on the condenser tube
walls.  Cooling towers also collect dust
and foreign materials that deposit in
the condenser tube.  The formation of
scale or sludge in the condenser is
indicated by a decrease water flow, low
temperature difference between inlet
and outlet water, and abnormally high
condensing temperatures.  To maintain
maximum condenser efficiency, the
condenser must remain free of built-
up scale and sludge, and may be
cleaned either mechanically or
chemically.

Customer Note

The use of improperly treated or
untreated water in this equipment may
result in scaling, erosion, corrosion,
algae or slime.  The services of a
qualified water treatment specialist
should be engaged to determine what
treatment, if any, is advisable.  Trane-
Ingersoll Rand warranty specifically
excludes liability for corrosion, erosion
or deterioration of Trane-Ingersoll
Rand equipment.  Trane assumes no
responsibilities for the results of the
use of  untreated or improperly treated
water, or saline or brackish water.

Summary of Contents for WCVS 12H

Page 1: ...ion Operation Maintenance Self Contained Water Cooled Air Conditioners WCVS SVX01A EN Aug 2012 Models WCVS 270 WCVS 330 WCVS 400 WCVS 470 WCVS 530 WCVS 600 WCVS 660 WCVS 730 WCVS 800 WCVS 900 WCVS 12H...

Page 2: ......

Page 3: ...he shipment Take photos of the damage material if possible Notify the carrier immediately by phone and registered mail Notify the local Trane Sales Office Concealed damage must be reported within 15 d...

Page 4: ...al Specification General Information Installation Operation Start up Coil Condenser Cleaning Trouble Analysis Guide Electrical Data Electrical Wiring Unit Dimensions Wiring Diagram Schematic Wiring Di...

Page 5: ...ory Minor Design Sequence C Double Wall PU Panels Standard on all models Introduction of FUJI Starter Factory Installed Options X None Installed Motor kW Refrigerent Type A R22 B R407c Future Use Serv...

Page 6: ...TRANE General Specification WCVS 270 12H 2...

Page 7: ...TRANE 3...

Page 8: ...e unit weights may be unevenly distributed Unit weights are provided in the general specification WARNING To prevent injury or death and unit damage observe handling cautions and procedures given in F...

Page 9: ...all a condenser main and standby water pump cooling tower pressure gauges strainers and all components for waterside piping All field installed piping must conform to applicable local codes Recommende...

Page 10: ...M Water Pressure Drop Ft H20 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 Water Pressure Drop Psi 96 96 96 Condenser 35 T Pressure Drop Vs GPM 2 31 3 31 4 31 5 31 6 31 7 31 8 31 9 31 10 31 11 31 12 31 13 3...

Page 11: ...60 70 80 90 100 110 120 130 140 150 160 170 180 GPM Water Pressure Drop Ft H20 0 1 0 6 1 1 1 6 2 1 2 6 3 1 3 6 4 1 4 6 5 1 5 6 Water Pressure Drop PSIG 96 96 96 96 Condenser Pressure Drop Vs GPM WCVS...

Page 12: ...n the Zone Sensor Thumbwheel to desired temperature setting Operation Unit start stop controls are provided on the facia of the unit mounted control box Unit is operated by pressing the START botton w...

Page 13: ...hould be checked and adjusted at least twice during the first few days of new belt operation Weekly maintenance Six month interval Required Unit Service Envelope The following summarizes the envelope...

Page 14: ...ype NFPA 90A and Residence Type Warm Air Heating and Air Conditioning Systems NFPA 90B or as perapplicable local codes Make duct connections to the unit with a flexible material such as heavy canvas I...

Page 15: ...TRANE Operation Start Up 11 Figure 4 Fan Duct Layout Comment Figure 5 A A A A R 6o minimum A A...

Page 16: ...d be provided or approved by the chemical supply house Caution Do not clean the refrigerant coil with hot water or steam The use of hot water or steam as a refrigerant coil cleaning agent will cause h...

Page 17: ...enser If condenser in changed Air in system Moisture in system Bad compressor Service valve closed if any Recover Re evacuate Re charge Recover Re evacuate Re charge or add refring Remove restriction...

Page 18: ...380 415V 3Ph 50Hz Over Size Fan Mtr 380 415V 3Ph 50Hz Over Size Fan Mtr 380 415V 3Ph 50Hz Over Size Fan Mtr 380 415V 3Ph 50Hz Over Size Fan Mtr 380 415V 3Ph 50Hz 380 415V 3Ph 50Hz Compr 1 Compr 2 Com...

Page 19: ...WIRING TO THE COMPRESSOR TERMINALS ARE CONNECTED IN THE CORRECT PHASE SEQUENCES PLEASE REFER DIAGRAM ON FIGURE 6 Figure 6 Scroll Compressors Terminal Wiring LINE 1 2 TO BE CONNECTED IN SERIES WITH CON...

Page 20: ...TRANE Unit Dimensions Water Cooled Vertical System WCVS 270 330 16...

Page 21: ...TRANE Unit Dimensions Water Cooled Vertical System WCVS 400 470 17...

Page 22: ...TRANE Unit Dimensions Water Cooled Vertical System WCVS 530 600 660 18...

Page 23: ...TRANE Unit Dimensions Water Cooled Vertical System WCVS 730 800 19...

Page 24: ...TRANE Unit Dimensions Water Cooled Vertical System WCVS 900 12H 20...

Page 25: ...TRANE Wiring Diagram With Starter WCVS 270 330 21...

Page 26: ...TRANE Schematic Wiring Diagram With Starter WCVS 400 22...

Page 27: ...TRANE Schematic Wiring Diagram With Starter WCVS 470 530 23...

Page 28: ...TRANE Schematic Wiring Diagram With Starter WCVS 600 660 730 800 24...

Page 29: ...TRANE Schematic Wiring Diagram With Starter WCVS 900 25...

Page 30: ...TRANE Schematic Wiring Diagram With Starter WCVS 12H 26...

Page 31: ......

Page 32: ...t office WCVS SVX01A EN August 2012 WCVS SVX01A EN February 2009 MALAYSIA R Trane has a policy of continuous product and product data improvement and reserves the right to change design and specificat...

Reviews: