66
System Troubleshooting (Continued)
Economizer Actuator (ECA) Test Procedures
Verify Economizer Status by Economizer Actuator (ECA)
LED indicator:
OFF:
No Power or Failure
ON:
Normal, OK to Economize
Slow Flash:
Normal, Not OK to Economize
Fast Flash:
½ Second ON/2 Seconds OFF:
Error Code:
Communications Failure
Pulse Flash
:
2 Seconds On/½ Second Off:
Error Code:
1 Flash:
Actuator Fault
2 Flashes:
CO
2
Sensor
3 Flashes:
RA Humidity Sensor out of range
4 Flashes
RA Temp Sensor out of range
6 Flashes
OA Humidity Sensor
7 Flashes
ECA not communicating with RTRM
8 Flashes
MA Temp Sensor
9-11 Flashes
Internal ECA failure
Method 2
Testing the LED with an analog Ohmmeter. Connect Ohm-
meter across LED in one direction, then reverse the leads
for the opposite direction. The LED should have at least 100
times more resistance in reverse direction, as compared
with the forward direction. If high resistance in both direc-
tions, LED is open. If low in both directions, LED is shorted.
Method 3
To test LED's with ZSM connected to the unit, test voltages
at LED terminals on ZSM. A measurement of 32 VDC,
across an unlit LED, means the LED has failed.
Note: Measurements should be made from LED
common (ZSM terminal 6 to respective LED
terminal). Refer to the Zone Sensor Module (ZSM)
Terminal Identification table at the beginning of this
section.
Programmable & Digital Zone Sensor Test
Testing serial communication voltage
1. Verify 24 VAC is present between terminals RTRM J6-14
and RTRM J6-11.
2. Disconnect wires from RTRM J6-11 and RTRM J6-12.
Measure the voltage between RTRM J6-11 and RTRM
J6-12; it should be approximately 32 VDC.
3. Reconnect wires to terminals RTRM J6-11 and RTRM
J6-12. Measure voltage again between RTRM J6-11 and
RTRM J6-12, voltage should flash high and low every
0.5 seconds. The voltage on the low end will measure
about 19 VDC, while the voltage on the high end will
measure from approximately 24 to 38 VDC.
4. Verify all modes of operation, by running the unit through
all of the steps in the “Test Modes" section discussed in
"Unit Start-Up".
5. After verifying proper unit operation, exit the test mode.
Turn the fan on continuously at the ZSM, by pressing the
button with the fan symbol. If the fan comes on and runs
continuously, the ZSM is good. If you are not able to turn
the fan on, the ZSM is defective.
Rooftop Refrigerator Module (RTRM)
Default Chart
CV Units
If the RTRM loses input from the building management sys-
tem, the RTRM will control in the default mode after approxi-
mately 15 minutes. If the RTRM loses the Heating and Cool-
ing Setpoint input from the potentiometers, the RTRM will
control in the default mode instantaneously. The tempera-
ture sensing thermistor in the Zone Sensor Module for CV
applications is the only component required for the "Default
Mode" to operate.
VAV Units
If the RTRM loses input from the building management sys-
tem, the RTRM will control in the default mode after approxi-
mately 15 minutes. For VAV units, a "shorted" mode input is
the only input required for the "Default Mode" to operate. If
the RTRM loses setpoint inputs from the RTAM due to re-
mote setpoint input failure, the RTRM will use default
setpoint inputs as defined in the default chart for VAV units.
Constant Volume Defaults
Component or Function
Default Operation
Cooling Setpoint (CSP)
74° F
Heating Setpoint (HSP)
71° F
Economizer Normal
Operation
Economizer Minimum
Normal Operation
Position
Normal operation, or auto if
Mode
ZSM mode switch has failed
Normal operation, or
Fan
continuous if fan mode
switch on ZSM has failed
Night Setback Mode
Disabled - Used with
Integrated Comfort™
System and Programmable
ZSM’s only
Supply Air Tempering
Disabled - Used with
Integrated Comfort™
Systems only
Variable Air Volume Defaults
Component or Function
Default Operation
Supply Air Cooling
Setpoint Failure
55° F
Supply Air Reset
Setpoint Failure
Disable Reset
Supply Air Reset Amount
Disable Reset
Supply Air Static
Setpoint Failure
0.5 IWC
Supply Air Static
Deadband Failure
0.5 IWC
Morning Warm-Up
Setpoint Failure
Disable MWU and DWU
Mode Failure "Open"
Unit Mode "Off"
Mode Failure "Shorted"
Unit Mode "Auto"
Summary of Contents for Voyager RT-SVX17C-EN
Page 8: ...8 Figure 1 Unit Dimensions for TC_ TE_ and YC_330 360 and 420 MBH Units Low Heat ...
Page 9: ...9 Figure 1 continued Unit Dimensions for YC_330 360 and 420 MBH Units High Heat ...
Page 10: ...10 Figure 1 continued Unit Dimensions for TC_ TE_ and YC_480 and 600 MBH Units Low High Heat ...
Page 24: ...24 Figure 10 Typical FieldWiring Requirements for CV Control Options ...
Page 78: ......
Page 79: ......
Page 80: ......