RT-SVX34R-EN
73
Table 45.
Test mode states for CV units with modulating hot gas reheat and modulating heat
TEST
STEP
MODE
FAN
ECON
COMP
1
COMP
2
COMP
3
HEAT
OUTPUT
PUMP-
OUT
COOL
VALVE
RE-
HEAT
VALVE
VAV
BOX
1
FAN ON
ON
MIN
OFF
OFF
OFF
OFF
OFF
100%
0%
ON
2
ECONO-
MIZER
ON
OPEN
OFF
OFF
OFF
OFF
OFF
100%
0%
ON
3
COOL 1
ON
MIN
ON
OFF
OFF
OFF
IN-
CONTROL
100%
0%
ON
4
COOL 2
ON
MIN
ON
ON
OFF
OFF
IN-
CONTROL
100%
0%
ON
5
COOL 3
ON
MIN
ON
ON
ON
OFF
IN-
CONTROL
100%
0%
ON
6
REHEAT
ON
MIN
ON
ON
ON
OFF
IN-
CONTROL
50%
50%
ON
7
HEAT 1
ON
MIN
OFF
OFF
OFF
50%
OFF
100%
0%
ON
8
HEAT 2
ON
MIN
OFF
OFF
OFF
100%
OFF
100%
0%
ON
9
RESET
Notes:2 & 3 stage standard efficiency units (excluding 40-50T Std Efficiency CV):
1
.
For 27.5-35T units, both compressors will be energized during the Cool 2 Step. For 40-50T units, only Compressor 2 will be energized
during the Cool 2 Step.
2
.
The Reheat Pumpout relay will be energized any time the Reheat circuit is energized in active Cooling Mode.
3
.
For units with Statitrac installed, the Exhaust Damper will track the Economizer position during Service Test Mode and the Exhaust Fan
will be energized once the Economizer rises above the Exhaust Enable Setpoint.
4
.
Heating will not be energized during Service Test until the 6 minute VAV Box ON timer has expired.
Notes:5 stage high efficiency units (including 40-50T Std Efficiency CV):
1
.
Compressor 1 is the smaller compressor on the circuit.
2
.
Condenser fans are controlled as defined for normal operation.
3
.
Exhaust fan operates as defined for normal operation based on economizer position.
4
.
When Compressor 1 is energized with either C1, C2, or with both for 30 minutes continuously, C3 will be required to de-energize for 30
seconds.